Datenblatt für RCP-2000 Series von MEAN WELL USA Inc.

MEAN WELL @(gcm EHI CBCEEE WE
Industrial automation
Distributed power architecture system
Wireless/telecommunication solution
Redundant power system
Electric vehicle charger system
Constant current source system
Model Encoding / Order Information
Description
RCP-2000 is a 2KW single output rack mountable front end AC/DC power supply with a 1U low profile
and a high power density up to 25W/inch . This series operates for 90~264VAC input voltage and offers
3
the models with the DC output mostly demanded from the industry. Each model is cooled by the built-in
DC fan with fan speed control, working for the temperature up to 70 . RCP-2000 provides vast design
flexibility by equipping various built-in functions such as the PMBus communication protocol, output
programming, active current sharing (up to 18000W via three 19 rack shelves, RKP-1U), remote control,
auxiliary power, alarm signal, external control/monitor via the control model RKP-CMU1, etc. Maximum
number that can be monitored by master controller in communication shall be 9 power supplies.
Universal AC input / Full range
(Withstand 300VAC surge input for 5 seconds)
Built-in active PFC function
High efficiency up to 92%
Forced air cooling by built-in DC fan
Output voltage programmable
Built-in OR-ing FET, support hot swap (hot plug)
Active current sharing up to 6000W for one 19 rack shelf
Built-in I C interface, PMBus protocol
2
Protections: Short circuit / Overload / Over voltage /
Over temperature
Optional conformal coating
5 years warranty
Features Applications
2000W Rack Mountable Front End Rectifier RCP-2000 series
Output wattage
Output voltage
24RCP - -2000
File Name:RCP-2000-SPEC 2021-05-04
Note 1: 19" rack shelf, RKP-1U, available. Details available on http://www.meanwell.com/
Note 2: Control/Monitor unit, RKP-CMU1, available. Details available on http://www.meanwell.com/
5
Dimension
L
295
11.6
W
127
H
41 (1U)
(1U)
mm
inch1.61
*
*
*
*
*
*
Series name
UL62368-1 TPTC004 IEC62368-1BS EN/EN62368-1
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
MW MEAN WELL
SPECIFICATION
RCP-2000-12 RCP-2000-24
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5,6
FREQUENCY RANGE
EFFICIENCY (Typ.)
POWER FACTOR (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
AC CURRENT (Typ.)
12V 24V
100A 80A
0 ~ 100A 0 ~ 80A
1200W 1920W
150mVp-p
10.5 ~ 14V
200mVp-p
21 ~ 28V
±2.0% ±1.0%
±1.0%
±1.0%
1500ms, 60ms/230VAC at full load
16ms/230VAC at 75% load 10ms/230VAC at full load
90 ~ 264VAC 127 ~ 320VDC
47 ~ 63Hz
86%
0.98/230VAC at full load
COLD START 50A
13A/115VAC 7A/230VAC 16A/115VAC 10A/230VAC 16A/115VAC 10A/230VAC
<1.1mA / 230VAC
RCP-2000-48
48V
42A
0 ~ 42A
2016W
300mVp-p
42 ~ 56V
±1.0%
±0.5% ±0.5%
±0.5% ±0.5%
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.4
90.5% 92%
Protection type : Constant current limiting, unit will shut down o/p voltage after 5 sec. re-power on to recover
OVER TEMPERATURE
OVERLOAD
OVER VOLTAGE
105 ~ 125% rated output power
14.7 ~ 17.5V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
29.5 ~ 35V 57.6 ~ 67.2V
PROTECTION
REMOTE SENSE
REMOTE ON-OFF CONTROL
AUXILIARY POWER
Compensate voltage drop on the load wiring up to 0.5V
Please refer to the Function Manual
5V @ 0.3A, 12V @ 0.8A
FUNCTION
Logic " High" for over temperature warning, Please refer to the Installation Manual, isolated signal
The isolated TTL signal out, Please refer to the Installation Manual
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-35 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RHnon-condensing
±℃ ℃0.03%/ (0 ~ 50 )
ENVIRONMENT
OVER TEMP WARNING
FAN FAIL SIGNAL
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
File Name:RCP-2000-SPEC 2021-05-04
2000W Rack Mountable Front End Rectifier
RCP-2000
series
SAFETY STANDARDS
WITHSTAND VOLTAGE
UL62368-1, CSA C22.2 , TUV EN62368-1 EAC TP TC 004 approved
BS EN/
,No. 62368-1
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC
ISOLATION RESISTANCE
MTBF
DIMENSION
PACKING
OTHERS
145.1K hrs min. Telcordia SR-332 (Bellcore) ; 37.4K hrs min. MIL-HDBK-217F (25 )
295*127*41mm (L*W*H)
SAFETY &
EMC
(Note 7)
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
2Kg; 6pcs/13Kg/1.04CUFT
NOTE 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
It will go back to normal ripple level once the output load is more than 10%.
4. Tolerance : includes set up tolerance, line regulation and load regulation.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. Please contact MEANWELL for 320~370VDC application.
7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.720 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
8. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Product Liability Disclaimer For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Adjustment of output voltage is allowable to 90 ~ 110% of nominal output voltage. Please refer to the Function Manual.
OUTPUT VOLTAGE PROGRAMMABLE
AC OK SIGNAL
DC OK SIGNAL
The isolated TTL signal out, Please refer to the Installation Manual
The isolated TTL signal out, Please refer to the Installation Manual
EMC IMMUNITY
EMC EMISSION
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
BS EN/ BS EN/
EN55024, EN61000-6-2
Standard
Standard
BS EN/
EN55032 (CISPR32)
BS EN/
EN55032 (CISPR32)
BS EN/
EN61000-3-2
BS EN/
EN61000-3-3
BS EN/
EN61000-4-2
BS EN/
EN61000-4-3
BS EN/
EN61000-4-4
BS EN/
EN61000-4-5
BS EN/
EN61000-4-6
BS EN/
EN61000-4-8
BS EN/
EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class B
Class A
-----
-----
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
MW MEAN WELL
84
85
86
87
88
89
90
91
92
93
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
PFC fosc : 110KHz
PWM fosc : 90KHz
Block Diagram
Static Characteristics
LOAD (%)
LOAD (%)
INPUT VOLTAGE (VAC) 60Hz
90 100 115 180
24V,48V
12V
264
90
100
80
70
75
65
50
40
Derating Loads vs Input Voltage
Efficiency vs Load (48V Model)
EFFICIENCY (%)
LOAD
The curve above is measured at 230VAC.
MODEL
INPUT 12V
1200W
1080W
1020W
960W
1920W
1632W
1440W
1248W
2016W
1713.6W
1512W
1310.4W
100A
90A
85A
80A
80A
68A
60A
52A
42A
35.7A
31.5A
27.3A
180~264VAC
115VAC
100VAC
90VAC
24V 48V
230VAC
Input only
-35 -25 0-10 15 30 50 60 70
20
40
60
50
80
100
(HORIZONTAL)
Derating Curve
AMBIENT TEMPERATURE ( )
2000W Rack Mountable Front End Rectifier RCP-2000 series
File Name:RCP-2000-SPEC 2021-05-04
LIMITING
ACTIVE
CURRENT
INRUSH
CONTROL
I/P RECTIFIERS
&
FILTER
SWITCHING
POWER
RECTIFIERS
FILTER
EMI
PWM CIRCUIT
DETECTION
POWER
AUX
&
PFC
FILTER
&
12V/0.8A
AUX POWER
PFC
CONTROL
5V/0.3A
AC-OK
MCU
DETECTION
CIRCUIT
O.V.P.
MCU
O.T.P.
DA/DB
PV
DC-OK
T-Alarm
SDA/SCL
REMOTE
ON-OFF
PM BUS
FAN FAIL
FAN
+V
-S
+S
RECTIFIERS
ORING
FET
-V
ORING FET
CONTROL
TRANSCEIVERS
DATA
ISOLATION
MW MEAN WELL
60
70
80
OUTPUT VOLTAGE(%)
90
100
110
Vout
0.50 1.5 3
EXTERNAL VOLTAGE (DC)
4.5 5 V
Function Manual
1.1 Remote Sense
1. Voltage Drop Compensation
The Remote Sense compensates voltage drop on the load wiring up to 0.5V
-V
+V
RCP-2000
+S
-S
LOAD
-V
+V
14
15
Sense lines should be twisted in pairs
+V
-V
+S
-S
RCP-2000
14
15
PIN14 +S
PIN14 +S
PIN15 -S
PIN15 -S
PV
-S
-V
+V
+S
RCP-2000
11
15
14
0~5V
-V Signal 9
LOAD
2000W Rack Mountable Front End Rectifier RCP-2000 series
File Name:RCP-2000-SPEC 2021-05-04
1.2 Local Sense
The +S,-S have to be connected to the ,-V , respectively, as the following diagram, in order to get the correct output voltage if Remote+V(signal) (signal)
Sense is not used.
In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 90~110% of the nominal voltage by applying
EXTERNAL VOLTAGE.
2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)
PIN9 -V(signal)
PIN11 PV
+S & +V, -S & -V also need to be connected on CN501
MW MEAN WELL
File Name:RCP-2000-SPEC 2021-05-04
2000W Rack Mountable Front End Rectifier RCP-2000 series
3. Remote ON-OFF Control
switch
PIN29 +5V-AUX
PIN17 Remote ON-OFF
The power supply can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.
4.PMBus Communication Interface
RCP-2000 supports PMBus Rev. 1.1 with maximum 100KHz bus speed, allowing information reading, status monitoring and output trimming. For
details, please refer to the Manual.Installation
Between andRemote ON-OFF +5V-AUX
Switch Short
Switch Open
Power Supply Status
ON
OFF
MW MEAN WELL I c
2000W Rack Mountable Front End Rectifier
RCP-2000
series
Mechanical Specification
Case No. 974A Unit:mm
direction
2.5
14.510
Air flow
295
SVR1
24
46
DC OK
5max.
41
7.112.5
127
61
26.2
3.6
62.4
Function
AC-OK
AC-NG
DC-OK
DC-NG
T-OK
T-ALARM
LED
GREEN
GREEN
GREEN
RED
RED
RED
Description
When input voltage 87V
When input voltage 75V
When output voltage 80% 5% of Vo rated.≧±
When output voltage 80% 5% of Vo rated.≦±
When the internal temperature (TSW1 & TSW2 short) is within safe limit
When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm
Signal
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
Power Supply
ON
OFF
ON
ON
ON
OFF
*
*Signal between function pin and "GND-AUX".
CN501
Input / Output Connector Pin No. Assignment( ) : Positronic PCIM34W13M400A1CN501
LED Status Indicators & Corresponding Signal at Function Pins
33
32 34
1357911 29
2468
10 13 31
12
13
11
15
16
14
18
19
17
21
22
20
24
25
23
27
28
26
30
31
29
Positive output voltage signal. For local sense only ; it cannot be connected directly to the load.
Negative output voltage signal. For local sense only ; it cannot be connected directly to the load.
Differential digital signal for parallel control. (Note.1)
The unit can turn the output on and off by electrical signal or dry contact between and . (Note.2)Remote ON-OFF +5V-AUX
Short (4.5 ~ 5.5V) : Power ON ; Open (0 ~ 0.5V) : Power OFF ; The maximum input voltage is 5.5V.
Serial Data used in the PMBus interface. (Note.2)
Serial Clock used in the PMBus interface. (Note.2)
Low (0 ~ 0.5V) : When the input voltage is 87Vrms.
High (4.5 ~ 5.5V) : When the input voltage in 75Vrms . The maximum sourcing current is 10mA and only for output. (Note.2)
Low (0 ~ 0.5V) : When Vout 80% 5%. The maximum sourcing current is 10mA and only for output. (Note.2)≧±
Low : When the internal fan is normal.(0 ~ 0.5V) The maximum sourcing current is 10mA and only for output(Note.2)
Connection for output voltage . (Note.1)
programming
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.(4.5 ~ 5.5V)
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature.(0 ~ 0.5V) The maximum sourcing
current is 10mA and only for output(Note.2)
Auxiliary voltage output, 4.5~5.5V, referenced to . The maximum load current is 0.3A.GND-AUX (pin 31)
Auxiliary voltage output, 10.8~13.2V, referenced to . The maximum load current is 0.8A.GND-AUX (pin 31)
This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
High (4.5 ~ 5.5V) : When the Vout 80% 5%.±
High : When the internal fan fail.(4.5 ~ 5.5V)
PMBus interface address lines. (Note.1)
Positive output terminal.
Negative output terminal.
Retain for future use.
Positive sensing
for remote sense.
Negative sensing
for remote sense.
Description
Pin No.
1,2,3,4
10
9
5,6,7,8
12,13
17
22
23
24
25
26
28
11
14
15
27
29
16,18,19,
20,21
Function
+V
+V(Signal)
-V(Signal)
-V
DA,DB
Remote
ON-OFF
NC
SDA
SCL
AC-OK
FAN-FAIL
PV
+S
-S
T-ALARM
+5V-AUX
A0,A1,A2,
A3,A4
Mating Housing Positronic PCIM34W13F400A1
31 GND-AUX Auxiliary voltage output GND.
The signal return is isolated from the output terminals (+V & -V).
This output has the built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
30 +12V-AUX
32 FG AC Ground connection.
DC-OK
33
34
AC/L
AC/N
AC Line connection.
AC Neutral connection.
Note1: Non-isolated signal, referenced to
-V(signal).
Note2: Isolated signal, referenced to .GND-AUX
File Name:RCP-2000-SPEC
2021-05-04
5
6.4
13
2