Datenblatt für MACX MCR-EX-T-UI-Upx von Phoenix Contact

www. hoenixconlacme calalo A A l I.-.O--0-00- [fl'c’gfir't'c’é 0-1 INSPIRING INNOVATIONS
© PHOENIX CONTACT 2012-05-21
104601_en_04
MACX MCR-EX-T-UI-UP...
Data sheet
1Description
The configurable and programmable MACX
MCR-EX-T-UI-UP... temperature transducer is used for the
intrinsically safe (Ex i) operation of all standard temperature
sensors (RTDs and thermocouples), voltage signals, re-
mote resistance-type sensors and potentiometers. The tem-
perature input signals are output in a linearized format at the
output. In addition to an analog current and voltage output,
the module also has a switching output. The power supply
has been designed as a wide range power supply.
The devices can be installed in zone 2 in the protection type
“n” (EN 60079-15).
The temperature transducer can be configured with the
standard configuration (see example: “Order key” on
page 6) or order-specific according to the order key and is
delivered calibrated and ready for operation. Possible set-
tings for the modules configured according to the order
(MACX MCR...-C) can be found in the order key on page
page 6.
The set configuration is shown on the label on the side of the
housing.
Features such as sensor type, connection method, measur-
ing range, measuring unit, filter, alarm signal and output
range can be configured using the IFS-CONF software and
a device-specific DTM (Device Type Manager).
Features
Input for all standard temperature sensors (RTDs and
thermocouples), voltage signals, remote resistance-
type sensors and potentiometers.
With intrinsically safe inputs [Ex ia] IIC
Current and voltage output
Switching output (1 PDT relay)
Configuration via software (FDT/DTM) or operator inter-
face (IFS-OP-UNIT)
Up to SIL 2 according to EN 61508 on output 4 ... 20 mA
3-way electrical isolation
Installation in zone 2 permitted
Wide range power supply 19.2 ... 253 V AC/DC
With screw or spring-cage connection
WARNING: Explosion hazard
The device is an item of associated electrical equipment for intrinsically safe circuits. It is designed for
use in zone 2, if specific conditions are observed.
When installing and operating the device, the applicable safety directives (including national safety directives), ac-
cident prevention regulations, as well as general technical regulations must be observed.
WARNING: Explosion hazard
Please observe the safety regulations and installation notes on page 11.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for the products listed in Section 3 “Ordering data” .
Temperature transducers with intrinsically safe
input for temperature sensors, voltage signals,
resistance-type sensors and potentiometers
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 2
2Table of contents
1 Description.................................................................................................................................. 1
2 Table of contents ........................................................................................................................ 2
3 Ordering data.............................................................................................................................. 5
4 Order key ................................................................................................................................... 6
5 Technical data ............................................................................................................................ 7
6 Minimum span and measuring accuracies.................................................................................. 9
6.1 Pt and Ni-RTD inputs........................................................................................................................................ 9
6.2 Cu-RTD inputs................................................................................................................................................... 9
6.3 NI1000 input (Landis & Gyr), KTY 81-110, KTY 84-130 (Philips) .............................................................. 9
6.4 Thermocouple input.......................................................................................................................................... 9
6.5 Cold junction error...............................................................................................................................9
6.6 Voltage signal input .......................................................................................................................................... 9
6.7 R transducers and resistors ............................................................................................................................ 9
6.8 Potentiometer .................................................................................................................................................. 10
6.9 Output signals ................................................................................................................................................. 10
7 Safety regulations and installation notes....................................................................................11
7.1 Installation and operation............................................................................................................................... 11
7.2 Safety regulations for installation in potentially explosive areas .............................................................. 11
7.3 Use in safety-related applications (SIL 2).................................................................................................... 12
8 Installation .................................................................................................................................13
8.1 Basic circuit diagrams ................................................................................................................................... 13
8.2 Structure........................................................................................................................................................... 13
8.3 Dimensions...................................................................................................................................................... 14
8.4 Mounting .......................................................................................................................................................... 14
8.5 Connecting the cables ......................................................................................................................14
8.6 Power supply ................................................................................................................................................... 14
8.7 Sensor types .....................................................................................................................................15
8.7.1 Thermocouple (TC) with internal cold junction compensation ...................................................................... 15
8.7.2 Thermocouple (TC) with external or without cold junction compensation.....................................................15
8.7.3 Voltage input ................................................................................................................................................ 15
8.7.4 Potentiometer............................................................................................................................................... 15
8.7.5 Resistance thermometer (RTD).................................................................................................................... 15
8.7.6 Measuring resistances ................................................................................................................................. 15
8.8 Current output ................................................................................................................................................. 15
8.9 Voltage output ................................................................................................................................................. 15
8.10 Switching output................................................................................................................................16
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 3
8.11 Switching output behavior with manual acknowledgement (latching) .................................................... 17
8.11.1 Switching behavior (2): Undertemperature limit ( SPH) .............................................................................. 17
8.11.2 (Switching behavior (3): Overtemperature limit ( SPH) ............................................................................... 17
8.11.3 Switching behavior (4): Undertemperature limit with hysteresis ( SPL) ...................................................... 18
8.11.4 Switching behavior (5): Overtemperature limit with hysteresis ( SPH)........................................................ 18
8.11.5 Switching behavior (6): Temperature range limit ( SPL and SPH) ........................................................... 19
8.11.6 Switching behavior (7): Temperature range limit ( SPL and SPH) ........................................................... 19
8.12 Monitoring function ......................................................................................................................................... 20
8.13 Operating modes ............................................................................................................................................ 20
8.13.1 SIL ON/SIL OFF ........................................................................................................................................... 20
8.13.2 Service mode ............................................................................................................................................... 20
9 Configuration .............................................................................................................................20
9.1 Delivered state/standard configuration........................................................................................................ 21
9.2 Zero adjust, adjustment via buttons S2 and S3 (only possible with SIL OFF) ....................................... 21
9.3 Span adjust, adjustment via buttons 2 and 4 (only possible with SIL OFF)............................................ 21
9.4 Force output......................................................................................................................................21
9.5 Cable compensation, 2-wire RTD or RTD 1 with 2 x RTD ........................................................................ 21
9.6 Cable compensation RTD 2 with 2 x RTD or TC with external cold junction compensation (TC + CJ
external) ........................................................................................................................................................... 22
9.7 Automatic potentiometer adjustment (teach-in) ......................................................................................... 22
9.8 Manual acknowledgement of switching outputs (latch function).............................................................. 22
9.9 LED status indicators ........................................................................................................................22
10 Password...................................................................................................................................23
11 Flow chart, operator interface ....................................................................................................23
11.1 Menu structure ................................................................................................................................................ 24
11.2 Key for start screen......................................................................................................................................... 25
11.3 Key for SETTINGS - MENU .......................................................................................................................... 25
11.4 Key for SETTINGS - Configure..................................................................................................................... 25
11.5 Key for SETTINGS - Service ......................................................................................................................... 26
11.6 Key for SETTINGS - Save ............................................................................................................................. 26
11.7 Key for input..................................................................................................................................................... 27
11.7.1 Key for input configuration (analog input) ..................................................................................................... 27
11.8 Key for output .................................................................................................................................................. 29
11.8.1 Key for output configuration (analog output)................................................................................................. 29
11.9 Key for error handling..................................................................................................................................... 30
11.10 Key for switch .................................................................................................................................................. 30
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 4
12 IFS-OP-UNIT operator interface error codes .............................................................................30
13 Configuration with the service PC ..............................................................................................31
13.1 System requirements ..................................................................................................................................... 31
13.2 Configuring the user characteristic curve ..........................................................................................31
14 Comparison of safety data .........................................................................................................31
15 Application examples.................................................................................................................32
15.1 Current output ................................................................................................................................................. 32
15.2 Voltage output ................................................................................................................................................. 32
15.3 Switching output.............................................................................................................................................. 33
Appendix
Safety-related applications (SIL 2) ............................................................................................................................. A-1
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 5
3Ordering data
Temperature transducer, Ex i
Description Type Order No. Pcs. / Pkt.
Standard configuration/in-stock article, with screw connection MACX MCR-EX-T-UI-UP 2865654 1
Standard configuration/in-stock article, with spring-cage connection MACX MCR-EX-T-UI-UP-SP 2924689 1
Order configuration/KMAT, with screw connection MACX MCR-EX-T-UI-UP-C 2811763 1
Order configuration/KMAT, with spring-cage connection MACX MCR-EX-T-UI-UP-SP-C 2924692 1
Accessories
Description Type Order No. Pcs. / Pkt.
Operator interface for the configuration of compatible MACX modules. IFS-OP-UNIT 2811899 1
Cradle unit, for snapping the operating and display unit onto the DIN rail IFS-OP-CRADLE 2811886 1
Programming adapter for MACX MCR... devices. With USB interface for pro-
gramming with the IFS-CONF software
IFS-USB-PROG-ADAPTER 2811271 1
Cold junction compensation connector for thermocouples MACX MCR-EX-CJC 2925002 1
For additional accessories, please refer to the INTERFACE catalog from Phoenix Contact.
m
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 6
4Order key
Order key for temperature transducer MACX-MCR-EX-T-UI-UP(-SP)-C (standard configuration entered as an example)
Order No. Safety Integrity
Level (SIL)
Sensor type Connection
method
Cold junction
compensation
Measuring range: Measuring
unit
Output range Factory calibration certificate
= FCC
Start End
2811763 / ON / PT100 / 4 / 0 / -50 / 150 / C / OUT02 / NONE
2811763
MACX MCR-EX-
T-UI-UP-C
ON active See below 2 2-wire 0 off, e.g. with
RTD, R,
potentiometer,
mV
See
below
See
below
C°C OUT15 0...5 mA NONE without FCC
F°F OUT16 0...10 mA
NONE not active O OUT01 0...20 mA
33-wire P %OUT150...5 mA YES with FCC (a fee is
charged)
2924692
MACX MCR-EX-
T-UI-UP-SP-C
VmV OUT25 1...5 mA
ON only with output
range = OUT02
1on, e.g. with TC OUT26 2...10 mA
44-wire OUT02 4...20 mA
OUT05 0...5 V YESPLUS Factory calibration
certificate with
5 measuring points
(a fee is charged)
OUT03 0...10 V
OUT06 1...5 V
OUT04 2...10 V
OUT13 -5...+5 V
OUT14 -10...+10 V
others freely
configurable in the
software
Smallest measuring
range
Other setting options can be configured
with the IFS-CONF software.
- Freely configurable user characteristic with
30 interpolation points
- Output behavior in the event of a short circuit,
sensor break, or overrange/underrange is
freely configurable or can be set according to
NE43 (standard configuration: NE43 upscale)
- Filter setting (standard configuration: 1)
- Restart after failsafe
(standard configuration: ON)
- Switching behavior: Switching output ?
(limit values, times, etc.) (standard
configuration: OFF)
Resistance thermometers RTD
Others can be selected or are freely
configured in the software.
PT100 Pt 100 acc. to IEC/EN 60751 -200 850 °C 20 K
PT200 Pt 200 acc. to IEC/EN 60751 -200 850 °C 20 K
PT500 Pt 500 acc. to IEC/EN 60751 -200 850 °C 20 K
PT1000 Pt 1000 acc. to IEC/EN 60751 -200 850 °C 20 K
PT100S Pt 100 acc. to Sama RC21-4-1966 -200 850 °C 20 K
PT1000S Pt 1000 acc. to Sama RC21-4-1966 -200 850 °C 20 K
PT100G Pt 100 acc. to GOST 6651 -200 850 °C 20 K
PT1000G Pt 1000 acc. to GOST 6651 -200 850 °C 20 K
PT100J Pt 100 acc. to JIS C1604/1997 -200 850 °C 20 K
PT1000J Pt 1000 acc. to JIS C1604/1997 -200 850 °C 20 K
NI100 Ni 100 acc. to DIN 43760/DIN IEC 60751 -60 250 °C 20 K
NI1000 Ni 1000 acc, to DIN 43760/DIN IEC 60751 -60 250 °C 20 K
NI100S Ni 100 acc. to Sama RC21-4-1966 -60 180 °C 20 K
NI1000S Ni 1000 acc. to Sama RC21-4-1966 -60 180 °C 20 K
NI1000L Ni 1000 (Landis & Gyr) -50 160 °C 20 K
CU10 Cu 10 acc. to Sama RC21-4-1966 -70 500 °C 100 K
CU50
Cu 50/Cu 100 acc. to GOST 6651 (
Ü
= 1.428)
-50 200 °C 100 K
CU53 Cu 53 acc. to GOST 6651 (Ü = 1.426) -50 180 °C 100 K
KTY81 KTY81-110 (Philips) -55 150 °C 20 K
KTY84 KTY84-130 (Philips) -40 300 °C 20 K
Thermocouples TC
Others can be selected in the software.
B acc. to IEC/EN 60584 (Pt30Rh-Pt6Rh) 500 1820 °C 50 K
Eacc. to IEC/EN 60584 (NiCr-CuNi) -230 1000 °C 50 K
J acc. to IEC/EN 60584 (Fe-CuNi) -210 1200 °C 50 K
Kacc. to IEC/EN 60584 (NiCr-Ni) -250 1372 °C 50 K
Nacc. to IEC/EN 60584 (NiCrSi-NiSi) -250 1300 °C 50 K
Racc. to IEC/EN 60584 (Pt13Rh-Pt) -50 1768 °C 50 K
Sacc. to IEC/EN 60584 (Pt10Rh-Pt) -50 1768 °C 50 K
Tacc. to IEC/EN 60584 (Cu-CuNi ) -200 400 °C 50 K
Lacc. to DIN 43760 (Fe-CuNi) -200 900 °C 50 K
Uacc. to DIN 43760 (Cu-CuNi) -200 600 °C 50 K
CA C ASTM JE988 (2002) 02315 °C 50 K
DA D ASTM JE988 (2002) 0 2315 °C 50 K
A1G A-1 GOST 8.585-2001 02500 °C 50 K
A2G A-2 GOST 8.585-2001 0 1800 °C 50 K
A3G A-3 GOST 8.585-2001 01800 °C 50 K
MG M GOST 8.585-2001 -200 100 °C 50 K
LG L GOST 8.585-2001 -200 800 °C 50 K
Remote resistance-type sensors R
(2-, 3-, 4-wire)
Others can be selected in the software.
RES03 Resistance 0...150  0150
10% of the selected
measuring range
RES05 Resistance 0...600  0 600
RES06 Resistance 0...1200 01200
RES09 Resistance 0...6250 0 6250
RES10 Resistance 0...12,500 012500
RES12 Resistance 0...50,000 0 50000
Potentiometers
3-wire
Others can be selected in the software.
POT03 Potentiometer 0...150  0100 %
10% of the selected
measuring range
POT05 Potentiometer 0...600  0 100 %
POT06 Potentiometer 0...1200 0100 %
POT09 Potentiometer 0...6250 0 100 %
POT10 Potentiometer 0...12,500 0100 %
POT12 Potentiometer 0...50,000 0 100 %
Voltage signals mV
Others can be selected in the software.
V04 Voltage (mV) -1000 +1000 mV 10% of nominal
span
9
T [°F] = T [°C] + 32
5
Temperature conversion guide for °C to °F:
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 7
5 Technical data
Input
Resistance thermometer Pt, Ni, Cu sensors: 2-, 3-, 4-wire
Thermocouple sensor B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
(see example, “Order key” on page 6)
Resistor 0 ... 50 k
Potentiometer 0 ... 50 k
Voltage -1000 mV ... 1000 mV
Output
Output signal 4 mA ... 20 mA with SIL ON
(further output signals can be configured with SIL OFF)
Maximum output signal
Voltage output
Current output
±11 V
22 mA
Load
Voltage output
Current output
10 k
600 (at 20 mA)
Behavior in the event of a sensor error According to NE 43 (or freely definable)
Switching output
Contact type 1 PDT contact
Contact material AgSnO2, hard gold-plated
Maximum switching voltage 30 V AC (30 V DC)
Maximum switching current 0.5 A (30 V AC) / 1 A (30 V DC)
Cycles
With ohmic load 1 x 105
General data
Supply voltage range 24 V ... 230 V AC/DC (-20%/+10%, 50/60 Hz)
Current consumption < 50 mA (24 V DC)
Power consumption < 1.5 W
Temperature coefficient 0.01 %/K, maximum
Step response (0 ... 99 %)
With SIL
Without SIL
Typ. 1000 ms
Typ. 700 ms
Transmission error, total < 0.1% (e.g., for PT100, 300 K span, 4 ... 20 mA)
Electrical isolation
Input/output
Input/power supply
Input/switching output
Output/power supply
Power supply/switching output
4-way, between input/output/power supply/switching output
375 V P (according to EN 60079-11)
375 V P (according to EN 60079-11)
375 V P (according to EN 60079-11)
300 V rms reinforced insulation (according to EN 61010/50178)
300 V rms reinforced insulation (according to EN 61010/50178)
Ambient temperature
Operation
Storage/transport
-20 °C ... +65°C
-40 °C ... +85°C
Permissible humidity (operation) 5% ... 95% (no condensation)
Shock 15g, IEC 60068-2-27
Vibration 5g, IEC 60068-2-6
Status indicators Green LED (supply voltage, PWR)
Red LED, flashing (cable error, sensor error, ERR)
Red LED (module error, ERR)
Yellow LED (switching output)
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 8
Housing material PA 66-FR
Color Green
Degree of protection IP20
Pollution degree 2
Dimensions (width x height x depth) 17.5 x 99 x 114.5 mm
Inflammability class according to UL 94 V0
Design Terminal housing for mounting on DIN rails
General data [...]
Conformance
EMC directive 2004/108/EC EN 61326-1; EN 61000-6-21; EN 61000-6-4
Ex directive (ATEX) EN 60079-0, EN 60079-11, EN 60079-15, EN 61241-0, EN 61241-11
1During the interference, there can possibly be small deviations.
Safety data according to ATEX for intrinsically safe circuits
Maximum voltage (Uo) 6 V
Maximum current (Io) 7.4 mA
Maximum power (Po) 11 mW
Gas group Ex ia IIC Ex ia IIB
Maximum external inductance (Lo) 100 mH 10 mH 1 mH 100 mH 10 mH 1 mH
Maximum external capacity (Co) 1.3 µF 1.7 µF 2.6 µF 6.8 µF 9.2 µF 15 µF
Maximum internal inductance (Ci) 44 nF 44 nF 44 nF 44 nF 44 nF 44 nF
Maximum internal inductance (Li) Negligible
Maximum voltage Um253 V AC (125 V DC)
Approvals
ATEX X II (1)G [Ex ia] IIC; X II (1)D [Ex iaD]
X II 3 G Ex nAC ic IIC / IIB / IIA T4 X
IBExU 10 ATEX 1044
IBExU 10 ATEX 1044
IECEx approval [Ex ia] IIC; [Ex iaD]; Ex nAC ic IIC T4 IECEx IBE 10.0004X
UL, USA/Canada Applied for
Functional safety (SIL) Can be used up to SIL 2
Connection data MACX MCR-EX-T-UI-UP
Conductor cross section
Solid (minimum/maximum)
Stranded (minimum/maximum)
AWG/kcmil (minimum/maximum)
0.2 mm2/2.5 mm2
0.2 mm2/2.5 mm2
24/14
Stripping length 7 mm
Connection method Plug-in screw connection
Tightening torque Minimum 0.5 Nm/maximum 0.6 Nm
Connection data MACX MCR-EX-T-UI-UP-SP
Conductor cross section
Solid (minimum/maximum)
Stranded (minimum/maximum)
AWG/kcmil (minimum/maximum)
0.2 mm2/1.5 mm2
0.2 mm2/1.5 mm2
24/16
Stripping length 8 mm
Connection method Spring-cage connection
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 9
6 Minimum span and measuring
accuracies
6.1 Pt and Ni-RTD inputs
Minimum measuring span:
With 10 R0 < 100 : 100 K
With 100 R0 10 k : 20 K
Measuring accuracy:
For 10 R0 < 100 : 0.2 K x 100 / R0
= 0.1% x (100 /R0) x (200 K/measuring span)
For 100 R0 1 k : 0.2 K
= 0.1% x (200 K/measuring span)
For 1 k < R0 10 k : 0.4 K
= 0.1% x (400 K/measuring span)
6.2 Cu-RTD inputs
Minimum measuring span:
For 10 R0 < 100 : 100 K
For 100 R0 10 k: 20 K
Measuring accuracy:
For 10 R0 < 100 : 0.5 K x 100 /R0
= 0.1% x (100 /R0) x (500 K/measuring span)
For 100 R0 1 k : 0.5 K
= 0.1% x (500 K/measuring span)
For 1 k < R0 10 k : 1.0 K
= 0.1% x (1000 K/measuring span)
6.3 NI1000 input (Landis & Gyr), KTY 81-110,
KTY 84-130 (Philips)
Minimum measuring span: 20 K
Measuring accuracy: 0.2 K
6.4 Thermocouple input
Minimum measuring span with TC: 50 K
Measuring accuracy of the input with TC signals:
TC type E, J, K, N, T, L, U, M, Lr
Without cold junction error: 0.30 K
TC types B, R, S, C, D, A1, A2, A3
Without cold junction error: 0.50 K
6.5 Cold junction error
Cold junction error: ± 1 K, maximum
(with internal cold junction compensation).
With external compensation it depends on the quality of the
cold junction and the sensor used.
6.6 Voltage signal input
Minimum measuring span:
10% of the nominal span of the respective range.
Measuring accuracy:
6.7 R transducers and resistors
50% of measuring range (nominal value of R transducer +
lead resistance) measuring range
Minimum measuring span: 10% of the selected measuring
range
Measuring accuracy:
Example:
R transducer with nominal value: 1000
Measuring range to be selected: 0 ... 1200
Minimum measuring span: 10% of the selected measuring
range = 120
Measuring accuracy: 0.01% of the selected measuring
range = 120 m
-1000 ... 1000 mV : 0.01% (of measuring range)
-500 ... 500 mV : 0.01% (of measuring range)
-250 ... 250 mV : 0.01% (of measuring range)
-125 ... 125 mV : 0.01% (of measuring range)
-60 ... 60 mV : 0.01% (of measuring range)
-30 ... 30 mV : 0.01% (of measuring range)
-15 ... 15 mV : 0.01% (of measuring range)
0 ... 75 : 0.10% (of measuring range)
0 ... 150 : 0.05% (of measuring range)
0 ... 300 : 0.02% (of measuring range)
0 ... 600 : 0.01% (of measuring range)
0 ... 1200 : 0.01% (of measuring range)
0 ... 2400 : 0.01% (of measuring range)
0 ... 4800 : 0.01% (of measuring range)
0 ... 6250 : 0.02% (of measuring range)
0 ... 12500 : 0.02% (of measuring range)
0 ... 25000 : 0.02% (of measuring range)
0 ... 50000 : 0.02% (of measuring range)
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 10
6.8 Potentiometer
50% of measuring range (nominal value of potentiometer
+ lead resistance) measuring range
Minimum measuring span: 10% of the selected measuring
range
Measuring accuracy:
Example:
Potentiometer with nominal value: 1000
Measuring range to be selected: 0 ... 1200
Minimum measuring span: 10% of the selected measuring
range = 120
Measuring accuracy: 0.02% of the selected measuring
range = 240 m
6.9 Output signals
Analog output error
0... 75: 0.10% (of measuring range)
0... 150: 0.05% (of measuring range)
0... 300: 0.02% (of measuring range)
0... 600: 0.02% (of measuring range)
0 ... 1200 : 0.02% (of measuring range)
0 ... 2400 : 0.02% (of measuring range)
0 ... 4800 : 0.02% (of measuring range)
0 ... 6250 : 0.10% (of measuring range)
0 ... 12500 : 0.10% (of measuring range)
0 ... 25000 : 0.10% (of measuring range)
0 ... 50000 : 0.10% (of measuring range)
2 mV 0.01% at -10 ... 10 V
2 mV 0.02% at 0 ... 10 V
4 µA 0.02% at 0 ... 20 mA
GD 99
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 11
7 Safety regulations and installation notes
7.1 Installation and operation
Follow the installation instructions.
When installing and operating the device, the applicable
safety directives (including national safety directives), acci-
dent prevention regulations, as well as general technical
regulations must be observed.
For safety data, please refer to this data sheet and the cer-
tificates (EC-type examination certificate, and other approv-
als, if necessary).
7.2 Safety regulations for installation in poten-
tially explosive areas
Regulations for intrinsically safe circuits
Installation in zone 2
Observe the specified conditions for use in potentially ex-
plosive areas.
WARNING: Sensor does not conform to the
specification
Make sure that the connected sensors are only
used in the specified area (see “Order key” on
page 6).
WARNING: Sensor wiring
Check the structure for functionally correct wiring
(see “Basic circuit diagrams” on page 13).
NOTE: Installation, operation, and maintenance
may only be carried out by qualified specialist per-
sonnel.
NOTE:
Do not open the device or making changes to it.
Do not repair the device yourself; replace it with
an equivalent device. Repairs may only be per-
formed by the manufacturer. The manufacturer is
not liable for damage resulting from violation.
NOTE: The IP20 degree of protection (IEC
60529/EN 60529) of the device is intended for
use in a clean and dry environment. Do not sub-
ject the device to mechanical and/or thermal
loads that exceed the specified limits.
NOTE: Only specified devices from Phoenix
Contact may be connected to the 12-pos. S-
PORT interface.
WARNING: Explosion hazard
The devices are approved for intrinsically safe (Ex
i) circuits up to zone 0 (gas) and Ex zone 20
(dust). The technical safety values of the intrinsi-
cally safe field devices have to match the specifi-
cations of this package slip or otherwise the EC-
type examination certificate.
WARNING: Explosion hazard
If the device has been used in non-intrinsically
safe circuits, it must not be used again in intrinsi-
cally safe circuits. Label the device clearly as be-
ing not intrinsically safe.
WARNING: Explosion hazard
If the device has been used in non-intrinsically
safe circuits, it must not be used again in intrinsi-
cally safe circuits. Label the device clearly as be-
ing not intrinsically safe.
WARNING: Explosion hazard
The device is associated equipment of the Ex-i
protection type and is suitable for installation in
zone 2.
WARNING: Explosion hazard
Install the device in a suitable, approved housing
with a minimum of IP54 degree of protection.
At the same time, observe IEC 60079-14/EN
60079-14 requirements.
WARNING: Explosion hazard
Disconnect the block power supply before:
Connecting or disconnecting cables of non-
intrinsically safe circuits.
WARNING: Explosion hazard
Use only category 3G modules (ATEX 94/9/EC).
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 12
Installation in areas with a danger of dust explosions
Connection to the intrinsically safe circuit in areas with
a danger of dust explosions (zones 20, 21 and 22) is only
permitted if the equipment connected to this circuit is ap-
proved for this zone (e.g., category 1D, 2D or 3D).
7.3 Use in safety-related applications (SIL 2)
When using the MACX MCR-EX-T-UI-UP... in safety-relat-
ed applications, observe the instructions in the appendix, as
the requirements differ for safety-related functions. .
WARNING: Explosion hazard
The device must be stopped and immediately re-
moved from the Ex area if it is damaged, was sub-
jected to an impermissible load, stored incorrectly
or if it malfunctions.
WARNING: Explosion hazard
The device is not designed for installation in ar-
eas with a danger of dust explosions.
WARNING: Explosion hazard
If, however, you wish to use the device in zone 22,
it must be installed in a housing that complies with
IEC/EN 61241-1. In doing so, observe the maxi-
mum surface temperatures. Observe the require-
ments of IEC/EN 61241-14.
NOTE: Install the device in a suitable housing
with IP54 protection.
The switching output is not intended for safety-re-
lated applications.
“we -I¢- U600 IIIIIIII 9 b0? , / X j X ”my ‘1 9500 ““““ 9 500500., momere r DDT/r7 reswslance the ‘ 7 7 7 7 7 7 z @ II/Ova \ \ \ rvam/ Sensor connecuon and polenliomelers 2m.- infn. 22 man Sensor connection - lhermocoup‘es and mV sources A m Figure 1 Figure 2 1nasn1 en on
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 13
8 Installation
8.1 Basic circuit diagrams
Figure 1 Sensor connection - resistance thermometers
and potentiometers
Figure 2 Sensor connection - thermocouples and mV
sources
8.2 Structure
Figure 3 Structure MACX MCR-EX-T-UI-UP
Figure 4 Structure MACX MCR-EX-T-UI-UP-SP
1Plug-in COMBICON connectors
2S-PORT (12-pos. programming interface)
3Button S3 (UP), adjustment and reset functions
4Button S2 (DOWN), adjustment and reset functions
5DIP switch S1 for service mode
6PWR LED, green, power supply
7DAT LED, green, no function at present
8LED ERR, red, module, cable and sensor error, under-
range or overrange, service mode
9DO LED, yellow, status of switching output
NOTE: Electrostatic discharge!
The device contains components that can be
damaged or destroyed by electrostatic discharge.
When handling the device, observe the neces-
sary safety precautions against electrostatic dis-
charge (ESD) according to EN 61340-5-1 and EN
61340-5-2.
Take precautions against electrostatic discharge
before opening the front cover.
PLC / DCS
passive
-
+
3.3
3.2
-
+
3.3
3.1
DI
11
12
14
2.3
2.1
2.2
Zone 2
IN OUT
Power
24V ...230V AC/DC
3.3
3.1
1.2
3.2
1.1
2.3
2.1
2.2
1.3
4.3
4.1
4.2
5.3
5.1
5.2
μC
S-PORT
GND
I
U
OUT
OUT
NC
Zone 0,1,2
Zone 20,21,22
Sensor / Field
4.3
4.1
4.2
5.3
5.1
5.2
ϑ
ϑ
Poti
4.3
4.1
4.2
ϑ
RTD
ϑ
ϑ
RTD1
RTD2
Zone 0,1,2
Zone 20,21,22
PLC / DCS
passive
-
+
3.3
3.2
-
+
3.3
3.1
DI
11
12
14
2.3
2.1
2.2
Zone 2
IN OUT
Power
24V ...230V AC/DC
3.3
3.1
1.2
3.2
1.1
2.3
2.1
2.2
1.3
4.3
4.1
4.2
5.3
5.1
5.2
μC
S-PORT
GND
I
U
OUT
OUT
NC
Sensor / Field
4.3
4.1
4.2
5.3
5.1
4.3
4.1
4.2
TC
-
+
CJ
MACX MCR-EX-CJC
TC
-
+
external
CJ
mV
5.2
PWR
DAT
ERR
DO
1
4.2
5.2
2.2
3.2
4.3
5.3
2.3
3.3
MACX MCR-EX-T-UI-UP
32825 Blomberg, Germany
MACX MCR–EX–T–UI–UP
Ord. No.: 2865654
Ex–Temperature Transducer/Ex–Temperaturmessumformer
Supply Voltage:
Input
Analog–Out
Digital–Out
Max. Values
24V ... 230V AC/DC
RTD, TC, mV, Poti, R
0 20mA / ± 10V
WARNING
DO NOT SEPARATE WHEN ENERGIZED
AND INSTALLED IN ZONE 2
www.phoenixcontact.com
see manual
(–20%...+10%, 50Hz/60Hz)
U = 253V
m
U = 253V
m
U = 6,0 V DC
O
T –20°...+65°C/–4°...+149°F
amb
0,5A (30V AC) / 1A (30V DC)
I = 7,4 mA
O
P = 11 mW
O
U=30V (Zone 2)
m
P=
1,5W
N
OUT
IN
GND
14
11
12
NC
I
out
U
out
1.1 2.1
5.1
3.1
4.1
1.2 2.2
5.2
3.2
4.2
1.3 2.3
5.3
3.3
4.3
+
S-PORT
μc
3.1 3.2 3.3
2.1 2.2 2.3
1.1 1.2 1.3
1
2
3
5
4
7mm 0,5-0,6 Nm
5-7 lb In
MACX MCR-...
PWR
DAT
ERR
DO
1
4.2
5.2
2.2
3.2
4.3
5.3
2.3
3.3
MACX MCR-EX-T-UI-UP-SP
3.1 3.2 3.3
1.1 1.2 1.3
2.1 2.2 2.3
32825 Blomberg, Germany
MACXMCR–EX–T–UI–UP–SP
Ord.–No.: 2924689
Ex–Temperature Transducer/Ex–Temperaturmessumformer
Supply Voltage:
Input
Analog–Out
Digital–Out
Max. Values
24V ... 230V AC/DC
RTD, TC, mV, Poti, R
0 20mA / ± 10V
WARNING
DO NOT SEPARATE WHEN ENERGIZED
AND INSTALLED IN ZONE 2
www.phoenixcontact.com
see manual
(–20%...+10%, 50Hz/60Hz)
U=253V
m
U = 253V
m
U=6,0V
DC
O
T –20°...+65°C/–4°...+149°F
amb
0,5A (30V AC) / 1A (30V DC)
I=7,4mA
O
P = 11 mW
O
U=30V (Zone 2)
m
P=
1,5W
N
OUT
IN
GND
14
11
12
NC
I
out
U
out
1.1 2.1
5.1
3.1
4.1
1.2 2.2
5.2
3.2
4.2
1.3 2.3
5.3
3.3
4.3
+
S-PORT
μc
1
6
7
9
8
8mm
MACX MCR-...-SP
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 14
8.3 Dimensions
Figure 5 Dimensions (in mm)
8.4 Mounting
Figure 6 Mounting and removal
Mount the module on a 35 mm DIN rail according to EN
60715.
Install the module in a suitable housing to meet the re-
quirements for the protection class.
Before startup, check for correct function and wiring of
the MACX MCR-EX-T-UI-UP..., in particular the wiring
and marking of the intrinsically safe circuits.
8.5 Connecting the cables
Screw terminal blocks (for MACX MCR-EX-T-UI-UP);
litz wires provided with ferrules.
Permissible cable cross section: 0.2 mm2 to 2.5 mm2
Spring-cage terminal blocks (for
MACX MCR-EX-T-UI-UP-SP); litz wires provided with
ferrules.
Permissible cable cross section: 0.2 mm2 to 1.5 mm2
Install intrinsically safe and non-intrinsically safe cables
separately.
Screw connection:
Insert the conductor into the corresponding con-
nection terminal block.
Use a screwdriver to tighten the screw in the open-
ing above the connection terminal block.
Spring-cage connection:
Insert a screwdriver into the opening above the
connection terminal block.
Insert the conductor into the corresponding con-
nection terminal block.
8.6 Power supply
The power supply has been designed as a wide range
power supply (19.2 ... 253 V AC/DC). The module is sup-
plied with voltage via connection terminal blocks 1.1 and
1.2.
WARNING: Explosion hazard
If the module has been used in non-intrinsi-
cally safe circuits, it must not be used again in
intrinsically safe circuits.
The module must be clearly labeled as non-intrin-
sically safe.
99 17,5
114,5
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 15
8.7 Sensor types
The sensor types that can be used and their specific proper-
ties can be found in Section “Order key” on page 6
Depending on the connection method, the following termi-
nal points are to be connected for temperature measure-
ment (see Figure 1 on page 13).
8.7.1 Thermocouple (TC) with internal cold junction
compensation
Thermocouple connection: Terminals 4.1 “+“, 4.2 “-“
8.7.2 Thermocouple (TC) with external or without
cold junction compensation
Thermocouple connection: Terminals 5.1 “+“, 5.2 “-“
8.7.3 Voltage input
Connection: Terminals 5.1 “+“, 5.2 “-“
8.7.4 Potentiometer
Connection: Terminals 4.1, 4.2, 4.3
8.7.5 Resistance thermometer (RTD)
2-wire connection method: Terminals 4.2, 4.3
The cable resistance can be compensated with the help
of the IFS-CONF PC program, the IFS-OP-UNIT opera-
tor interface or in service mode (DIP switch).
3-wire connection method: Terminals 4.1, 4.2, 4.3
In the case of the 3-wire connection method, ensure
that all three cable resistances are the same.
4-wire connection method: Terminals 4.2, 4.3, 5.1, 5.2
2 x 2-wire connection method
Terminals RTD 1: 4.2, 4.3
Terminals RTD 2: 5.1, 5.2
8.7.6 Measuring resistances
The terminal points 4.2 and 4.3 are used for measuring dif-
fering resistances.
8.8 Current output
The current output can be freely configured between 0 and
20 mA. The minimum span is 4 mA. In safety-related appli-
cations (SIL = ON), the output is fixed at 4 ...20 mA.
Connection: Terminals 3.2 “+“, 3.3 “-“
8.9 Voltage output
The voltage output can be freely configured between -10
and +10 V. The minimum span is 2 V.
Connection: Terminals 3.1 “+“, 3.3 “-“
Use the MACX MCR-EX-CJC cold junction com-
pensation connector provided (Order No.
2925002).
TC+CJ: Use the cold junction compensation con-
nector provided at connection terminal blocks
4.1, 4.2 and 4.3.
TC+CJ external: Use the external cold junction
compensation sensor (e.g., PT100) at connection
terminal blocks 4.2 and 4.3.
RL 25 for each lead.
Up to 75 : RL 2.5 for each lead.
Up to 150 : RL 5 for each lead.
Up to 300 : RL 10 for each lead.
The voltage output cannot be used for safety-re-
lated applications (SIL = ON).
I T E3
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 16
8.10 Switching output
Switching output 1 has one PDT. The behavior of the switch-
ing output can be selected. The switching points SPL1 and
SPH2 can be configured across the entire sensor range:
Switching behavior of the switching output
.
Switching behavior 0
Switching output is permanently
dropped.
Switching behavior 1
Switching output is permanently
picked up.
Switching behavior 2
Switching output picks up when SPH2
is exceeded.
Switching behavior 3
Switching output drops out when SPH2
is underrange.
Switching behavior 4
Switching output picks up when SPL2
is exceeded and drops out when SPH1
is underrange (hysteresis).
Switching behavior 5
Switching output drops out when SPL2
is exceeded and picks up when SPH1
is underrange (hysteresis).
1
0
1
0
SPH
0
1
1
0
SPH
0
1
SPL SPH
0
1
SPL SPH
Switching behavior 6
Switching output picks up between
SPL1 and SPH2.
Switching behavior 7
Switching output drops out between
SPL1 and SPH2.
1SPL = Set Point Low (lower switching point)
2SPH = Set Point High (upper switching point)
The switching output is not intended for safety-re-
lated applications.
If only the switching output is to be used, the cur-
rent output (connection terminal blocks 3.2 and
3.3) must be short circuited or subjected to a load.
1
0
SPL SPH
1
0
SPL SPH
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 17
8.11 Switching output behavior with manual ac-
knowledgement (latching)
8.11.1 Switching behavior (2): Undertemperature limit
( SPH)
8.11.2 (Switching behavior (3): Overtemperature limit
( SPH)
Latching: No automatic restart after exceeding
limit value (SPH: SET Point High) or falling below
limit value (SPL: Set Point Low).
Disable the option “Restart after fail safe” in the
configuration software.
Normal operating state > SPH
Step Measure
1Measured
value
> SPH and module are acti-
vated
2Relay ON
3Measured
value
SPH
4Relay OFF
5Measured value> SPH
6 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
Critical operating state SPH
Step Measure
1Measured
value
SPH and module are acti-
vated
2Relay OFF
3Measured
value
> SPH
4 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
SPH
0
1
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Normal operating state < SPH
Step Measure
1Measured
value
< SPH and module are acti-
vated
2Relay ON
3Measured
value
SPH
4Relay OFF
5Measured value< SPH
6 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
Critical operating state SPH
Step Measure
1Measured
value
SPH and module are acti-
vated
2Relay OFF
3Measured
value
< SPH
4 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
1
0
SPH
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
4:3“
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 18
8.11.3 Switching behavior (4): Undertemperature limit
with hysteresis ( SPL)
8.11.4 Switching behavior (5): Overtemperature limit
with hysteresis ( SPH)
Normal operating state > SPL
Step Measure
1Measured
value
> SPL and module are acti-
vated
2Relay ON
3Measured
value
SPL
4Relay OFF
5Measured value> SPH
6 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
Critical operating state SPL
Step Measure
1Measured
value
SPL and module are acti-
vated
2Relay OFF
3Measured
value
> SPH
4 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
0
1
SPL SPH
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Normal operating state < SPH
Step Measure
1Measured
value
< SPH and module are acti-
vated
2Relay ON
3Measured
value
SPH
4Relay OFF
5Measured value< SPL
6 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
Critical operating state SPH
Step Measure
1Measured
value
SPH and module are acti-
vated
2Relay OFF
3Measured
value
< SPL
4 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
0
1
SPL SPH
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
+31
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 19
8.11.5 Switching behavior (6): Temperature range lim-
it ( SPL and SPH)
8.11.6 Switching behavior (7): Temperature range lim-
it ( SPL and SPH)
Normal operating state > SPL and < SPH
Step Measure
1Measured
value
> SPL and < SPH module
are activated
2Relay ON
3Measured
value
SPL or SPH
4Relay OFF
5 Measured value > SPL or < SPH
6 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
Critical operating state SPL and SPH
1Measured
value
a) SPL and module are acti-
vated
b) SPH and module are acti-
vated
2Relay OFF
3Measured
value
a) > SPL and < SPH
b) < SPH and > SPL
4 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
1
0
SPL SPH
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Normal operating state < SPL and > SPH
Step Measure
1Measured
value
a) < SPL and module are acti-
vated
b) > SPH and module are acti-
vated
2Relay ON
3Measured
value
a) SPL and SPH
b) SPH and SPL
4Relay OFF
5 Measured value < SPL or > SPH
6 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
Critical operating state SPL and SPH
Step Measure
1Measured
value
SPL and SPH and mod-
ule are activated
2Relay OFF
3Measured
value
< SPL or > SPH
4 Relay Remains OFF (latches) until
delay time has passed and
then acknowledged manu-
ally
1
0
SPL SPH
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Acknowledgement is only possible when
there is no critical state anymore and the de-
lay time has passed.
Configuration 9 A WARNING: Explo When configunng in approved for use in zone Figure 7 Posihon loe DI i]
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 20
8.12 Monitoring function
The temperature transducer is equipped with monitoring
functions for the input and output range.
Input monitoring function
The input monitoring function for line break and short circuit
refers to the sensor connected to the input. When an error is
detected, the output signal is set to the configured error
value. In the case of RTD sensors and resistance-type sen-
sors, short-circuit failures are detected resistance values <
1 .
Short circuits of thermocouples and mV sources cannot be
detected, since 0 V can be a valid signal.
On RTD sensors, resistance-type sensors and potentiome-
ters, a line break is detected when the current flow through
the sensor is faulty.
As soon as the fault has been eliminated, the temperature
transducer continues to perform its normal functions. (see
“LED status indicators” on page 22, Line faults)
Output monitoring function
The current output can be monitored for line breaks and
maximum load. This is activated via the configuration. In
safety-related applications (SIL = ON), the output monitor-
ing is always active. The voltage output is not monitored. As
soon as the fault has been eliminated, the temperature
transducer continues to perform its normal functions. (see
“LED status indicators” on page 22, Line faults)
8.13 Operating modes
8.13.1 SIL ON/SIL OFF
The temperature transducer can either be operated in SIL
ON or SIL OFF. The standard configuration is SIL ON with
DIP switch S1 set to the OFF position. With the order config-
uration, customer-specific configurations can be selected in
the order key (see “Order key” on page 6).
8.13.2 Service mode
Service mode can be selected at any time via the
IFS-OP-UNIT operator interface and the configuration soft-
ware, e.g., IFS-CONF or via DIP switch S1.
If settings are changed during service mode and service
mode is then exited, the temperature transducer performs a
warm start in order to apply the newly set values. If no
changes are made, the transducer starts up in normal mea-
suring mode without a warm start. The switching output
switches according to its configuration.
In service mode, it is also possible to simulate the output sig-
nal independently of the input signal (force). In this case, in
safety-related applications the safety function of the device
is deactivated and the initial value for the analog output sig-
nal is 2 mA, which allows subsequent devices to detect the
deviation from normal operation as a result of the measured
value being underrange.
During service mode, the switching output is deactivated
and remains in its idle position.
9Configuration
Figure 7 Position of the DIP switch and buttons
If the configuration is modified using the
IFS-OP-UNIT operator interface and PC-based
software (e.g., IFS-CONF) or via DIP switch, the
changes made must always be checked again
and released before transfer to the temperature
transducer.
After the transfer, the new data in the temperature
transducer is applied by means of activation and
a warm start.
WARNING: Explosion hazard
When configuring in zone 2, the PC used must be
approved for use in zone 2.
When a DIP switch from S1-2 ... S1-8 (ON) is
switched on, the device is switched to service
mode. The red ERR LED flashes (1.2 Hz) and a
diagnostic I/O fault is displayed in the start
screen.
PWR
DAT
ERR
DO
1
4.2
5.2
2.2
3.2
4.3
5.3
2.3
3.3
MACX MCR-EX-T-UI-UP
ess
umformer
ut
DigitalOut
Max. Values
R
mA
/ ± 10V
WARNING
DO NOT SEPARATE WHEN ENERGIZED
AND INSTALLED IN ZONE 2
www.phoenixcontact.com
see manual
U=
253V
m
U= 6,0 V DC
O
T20°...+65°C/4°...+14F
amb
0,5A (30V AC) / 1A (30V DC)
I= 7,4 mA
O
P= 11 mW
O
U= 30V (Zone 2)
m
OUT
IN
GND
14
11
12
NC
I
out
U
out
1.12.1
5.1
3.1
4.1
1.22.2
5.2
3.2
4.2
1.32.3
5.3
3.3
4.3
+
S-PORT
μc
S1
S2
S3
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 21
9.1 Delivered state/standard configuration
9.2 Zero adjust, adjustment via buttons S2
and S3 (only possible with SIL OFF)
Set the adjustment by setting DIP switch S1-2 to ON.
Observe the analog output and set it with button S2 (de-
scending value) or S3 (ascending value)
or
press the buttons S2 and S3 simultaneously time for >
3 seconds to reset the cable compensation.
Save the set value by setting DIP switch S1-2 back to
OFF.
9.3 Span adjust, adjustment via buttons 2 and
4 (only possible with SIL OFF)
Set the adjustment by setting DIP switch S1-3 to ON.
Observe the analog output and set it with button S2 (de-
scending value) or S3 (ascending value)
or
press the buttons S2 and S3 simultaneously time for >
3 seconds to reset the cable compensation.
Save the set value by setting DIP switch S1-3 back to
OFF.
Pressing buttons S2 and S3 simultaneously for > 3 sec-
onds resets the adjustment.
9.4 Force output
Set the adjustment by setting DIP switch S1-4 to ON.
Observe the analog output and set with the S2 (de-
scending value) or S3 (ascending value) button.
The specification/simulation is reset and ended by set-
ting DIP switch S1-4 back to OFF.
9.5 Cable compensation, 2-wire RTD or RTD 1
with 2 x RTD
Set the cable compensation RTD 1 via DIP switches
S1-1 to OFF and
S1-5 to ON.
Short circuit the sensor.
Apply the current measured value as the cable resis-
tance by pressing the S2 button.
Save the set value by setting DIP switch S1-5 back to
OFF.
Pressing buttons S2 and S3 simultaneously for > 3 seconds
resets the cable compensation.
Switch position DIP-S1
12345678
OFFOFFOFFOFFOFFOFFOFFOFF
Switch position DIP-S1
12345678
OFF ON OFF OFF OFF OFF OFF OFF
Switch position DIP-S1
12345678
OFF OFF ON OFF OFF OFF OFF OFF
When SIL is activated, the analog output starts at
2 mA and the switching output is deactivated.
Switch position DIP-S1
12345678
OFF OFF OFF ON OFF OFF OFF OFF
Switch position DIP-S1
12345678
OFF OFF OFF OFF ON OFF OFF OFF
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 22
9.6 Cable compensation RTD 2 with 2 x RTD or
TC with external cold junction compensa-
tion (TC + CJ external)
Set the cable compensation RTD 2 via DIP switches
S1-1 to ON and
S1-5 to ON.
Short circuit the sensor.
Apply the current measured value as the cable resis-
tance by pressing the S2 button.
Save the set value by setting DIP switches S1-1 and S1-
5 back to OFF.
Pressing buttons S2 and S3 simultaneously for > 3 seconds
resets the cable compensation.
9.7 Automatic potentiometer adjustment
(teach-in)
Set the teach-in by setting DIP switch S1-6 to ON.
Set potentiometer to start of range.
Press the S2 button.
Set potentiometer to end of range.
Press the S3 button.
Save the new measuring range by setting
DIP switch S1-6 back to OFF.
Pressing buttons S2 and S3 simultaneously for > 3 seconds
resets both values.
9.8 Manual acknowledgement of switching
outputs (latch function)
Set manual acknowledgment by setting DIP switch S1-
7 to ON.
Press buttons S2 and S3 simultaneously for > 3 sec-
onds.
Reset DIP switch S1-7 to OFF.
9.9 LED status indicators
Figure 8 LED status indicators
Switch position DIP-S1
12345678
ON OFF OFF OFF ON OFF OFF OFF
Switch position DIP-S1
12345678
OFFOFFOFFOFFOFF ON OFF OFF
Switch position DIP-S1
12345678
OFFOFFOFFOFFOFFOFF ON OFF
No. LED Color Description
6 PWR Green Supply voltage
ON Indicates the readiness for opera-
tion of the temperature trans-
ducer if supply voltage is avail-
able.
The temperature transducer is
configured without device supply
via programming adapter IFS-
USB-PROG-ADAPTER.
7 DAT Green No function at present
8 ERR Red Error
ON Module error
Flashing
(1.2 Hz)
Service mode active
flashing
(2.4 Hz)
Line fault
9 DO Yellow Switching output 1
ON Switching output active
PWR
DAT
ERR
DO
1
4.2
5.2
2.2
3.2
4.3
5.3
2.3
3.3
MACX MCR-EX-T-UI-UP-SP
3.1 3.2 3.3
1.1 1.2 1.3
2.1 2.2 2.3
32825 Blomberg, Germany
MACX MCREXTUIUPSP
Ord.No.: 2924689
ExTemperature Transducer/ExTemperaturmessumformer
Supply Voltage:
Input
AnalogOut
DigitalOut
Max. Values
24V ... 230V AC/DC
RTD, TC, mV, Poti, R
020mA / ± 10V
WARNING
DO NOT SEPARATE WHEN ENERGIZED
AND INSTALLED IN ZONE 2
www.phoenixcontact.com
see manual
(20%...+10%, 50Hz/60Hz)
U= 253V
m
U= 253V
m
U= 6,0 V DC
O
T20°...+65°C/4°...+14F
amb
0,5A (30V AC) / 1A (30V DC)
I= 7,4 mA
O
P= 11 mW
O
U= 30V (Zone 2)
m
P= 1,5W
N
OUT
IN
GND
14
11
12
NC
I
out
U
out
1.12.1
5.1
3.1
4.1
1.22.2
5.2
3.2
4.2
1.32.3
5.3
3.3
4.3
+
S-PORT
μc
6
7
9
8
EAAAG
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 23
10 Password
The device is protected by means of a four-digit password
set in the factory in order to prevent impermissible changes
to the configuration.
Default setting: 1111
If, however, only data from the device is to be displayed or
the device is to be used in non-safety-related applications,
the password can be deactivated.
Setting: 0000
The device can be accessed either via the IFS-OP-UNIT
(Order No.: 2811899) or via a service PC with connected
programming adapter IFS-USB-PROG-ADAPTER (Order
No.: 2811271) and the IFS-CONF configuration software.
11 Flow chart, operator interface
Configuration with the IFS-OP-UNIT
If you wish to use the MACX MCR-EX-T-UI-UP in combina-
tion with the IFS-OP-UNIT and with the IFS-OP-CRADLE,
the various operating functions that can be selected are
shown in the display.
Example: Display of SIL ON
Example: Display of SIL OFF
For safety-related applications, the password set
in the factory must always be changed.
If the password is lost, it is not possible to reset it.
In this case, please contact Phoenix Contact.
Further information on configuration with the
IFS-OP-UNIT or the IFS-CONF configuration
software can be found in the relevant user manu-
al.
WARNING: If Functional Safety is activated by a
reconfiguration or changes are made to the active
Functional Safety configuration, the rules under
Installation and startup must be observed.
WARNING: Limitations on safety-related ap-
plications
Only 4 ... 20 mA, limited programming of output
current in the event of line faults
(2 mA IOut 3.6 mA or IOut 21 mA)
WARNING: Once new configuration data has
been written, the device performs a warm start
that changes the properties of the device. The fol-
lowing control device must be adapted to these
modifications.
NOTE: Transfer and activate the configuration af-
ter the password has been changed.
When active, the SIL functionality is displayed in
the start screen.
For safety reasons, the SIL function cannot be
switched on again via the IFS-OP-UNIT operator
interface.
SIL can be switched off/deactivated via the SIL
OFF menu item.
To reactivate/switch on the SIL function, PC-
based configuration software, e.g., IFS-CONF is
required.
If no input is entered for five minutes during con-
figuration, the configuration is ended and any un-
saved data will be lost.
INPUT 1
SIL OK
INPUT 1
OK
J—JIIJJ JIIJ J I J J I I I AV C n L H
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 24
11.1 Menu structure
only 2 x RTD2 only 2 x RTD2
and differential measurement
OK / ESC
OK / ESC
OK
OK / ESC OK / ESC OK / ESC
OK / ESC OK / ESC
OK / ESC
OK / ESC
OK / ESC
OK / ESC
OK / ESC
OK / ESC
SettingsConfigure InputInput Conf
Output
Err.handl.
Service
Save
Password
Transfer
Save Conf
Password
Activate
Backup
Outp. Conf
BacklightCJ on/off
LanguageCJ Value
Temp-Unit
Filter
2W-Comp.C1
2W-Comp.C2
Restore
OK / ESC OK / ESC
Switch Switch 1On-Delay
Off-Delay
Acknowled.
Linebreak
Shorted
Input 1Input 2Input Diff
Output
Start ScreenSettings
Modul-
information
Diagnostic
Check
B/LB
Reset Cor.
Restart
Modul
Change PW
Reset
SIL OFF
Reset SW1
=== SEQ S
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 25
11.2 Key for start screen
Display of input and output signals, module and diagnostic information.
11.3 Key for SETTINGS - MENU
11.4 Key for SETTINGS - Configure
Display of the actual value of input 1
Display of the actual value of input 2, only if a second RTD is configured with the 2-wire connection
method.
Display of the actual value of the differential measurement with 2 x RTD with the 2-wire connection
method.
Display of the actual value of the analog output
Display of module information (order designation, firmware version, config version)
Module diagnostics (simulation, module error, I/O error)
The active configuration is read out from the module.
Setting for the background illumination (on, off, autodim)
Setting for the menu language (English, German)
Configuration of input, output, fault behavior and switching outputs
Input 1
Input 2
Input Diff
Output
Modul-
information
Diagnostic
Settings
Backlight
Language
Configure
® 3 . 3ng H3 Egg“
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 26
11.5 Key for SETTINGS - Service
11.6 Key for SETTINGS - Save
Access to the menu items of the service area
Input of a 4-digit numeric password in order to open the service area
(if the password is 0000, the password prompt is switched off)
Access to the menu items for the backup and restore functionality of the module configuration
Resets switching output 1 when it is snapped on (latching behavior)
Changes the set password
(change only becomes effective when the configuration has been transmitted to the module and acti-
vated)
Changes the setting from SIL ON to SIL OFF.
Resets the IFS-OP-UNIT and the connected module.
Saves the active configuration of the connected, compatible module in the IFS-OP-UNIT operator inter-
face (copy function)
Transmits the saved module configuration from the internal memory of the IFS-OP-UNIT operator inter-
face to the connected module (copy function).
Access to the menu items for the transmission and activation of the module configuration
Transmits the configuration from the IFS-OP-UNIT operator interface to the connected module
Input of a 4-digit numeric password in order to transmit the configuration
(if the password is 0000, the password prompt is switched off).
Activation of the module configuration (Yes/No)
Service
Password
Save Conf
Reset SW1
Change PW
SIL OFF
NOTE: It is only possible to switch on the SIL function via PC-based configuration software,
e.g., IFS-CONF.
Reset
Backup
Restore
Then activate the configuration by selecting Yes in the Activate menu item.
Save
Transfer
Password
Activate
Following activation, the module performs a warm start.
Q 595% m. L ], Hfi‘HH WM fi *[HH
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 27
11.7 Key for input
11.7.1 Key for input configuration (analog input)
Configuration selection, input configuration
Access to the menu items for the configuration of the input
(see “Key for input configuration (analog input)” on page 27)
Input
Setting for the dependent parameters of the input mode, sensor type, start and end of range, associated
inputs, switching behavior, switching points
Cold junction compensation with TC + CJ and TC + CJ ext. (on, off)
Correction of the cold junction value with CJ = On,
specification of the cold junction value with CJ = Off (-20 ... 65 K).
Setting for the temperature unit (°C, °F)
Setting for the filter factor (1 ... 10)
Setting for the cable resistance for RTD 2-wire connection method, channel 1 (0 ... 50 ).
Setting for the cable resistance for RTD 2-wire connection method, channel 2 (0 ... 50 ).
Input Conf
CJ on/off
CJ Value
Temp-Unit
Filter
2W-Comp.C1
2W-Comp.C2
Input Conf
Diff REnd
RStart IN1
Con. IN AO Con. IN SW1 Mode SW1 SPL SW1 SPH SW1
REnd IN2 Difference
Sensortype
CJ Sensor
Diff RStart
REnd IN1
RStart IN2
RTD Base
CJ RTDBase
Varialble RTD
Base
Varialble RTD
Base
Difference
ESC OKOK
OK
OKOKOKOKOKOKOK
OKOK
OKOK
OK
OK
OK
Y
Y
Y
N
N
N
Input Configuration
Mode= 2x RTD2
Mode= TC + CJ extern
Input Conf
Input Conf
ESC OK
2 $8ng BQQBEQ
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 28
Setting for the sensor mode
(RTD4, RTD3, RTD2, 2 x RTD2, TC + CJ, TC + CJ ext., potentiometer, mV).
Setting for the sensor type depending on sensor mode
(Pt, Ni, CU, KTY..., USER, for more see “Order key” on page 6).
RTD basic resistance for sensor types with a variable basic resistance
(e.g., when 100 is selected, the basic resistance is 100 )
Start of range for input 1 depending on sensor type, e.g., -50°C (°C, °F, , %, mV).
End of range for input 1 depending on sensor type, e.g., 150°C (°C, °F, , %, mV)
Start of range for input 2 depending on sensor type and only for 2 x RTD with 2-wire connection method,
e.g., -50°C (°C, °F, ).
End of range for input 2 depending on sensor type and only for 2 x RTD with 2-wire connection method,
e.g., 150°C (°C, °F, )
Setting for the differential measurement only for 2 x RTD with 2-wire connection method and not resis-
tance
(off, differential, absolute value differential)
Start of range for differential, only with differential and absolute value differential (°C, °F)
End of range for differential, only with differential and absolute value differential (°C, °F)
Sensor type of the cold junction, only with TC + CJ ext.
RTD basic resistance of the cold junction, only with TC + CJ ext.
Associated input of the analog output (input 1, input 2, differential), appears only in sensor mode 2 x RTD2
(2 x RTD 2-wire connection method)
Associated input of the switching output (input 1, input 2, differential), appears only in sensor mode 2 x
RTD2 (2 x RTD 2-wire connection method)
Mode of switching output (0 ... 7)
(see “Switching output” on page 16)
Setpoint low of switching output (appears only if mode > 3)
(see “Switching output” on page 16).
Setpoint high of switching output (appears only if mode > 1)
(see “Switching output” on page 16)
Input Conf
Sensortype
RTD Base
RStart IN1
REnd IN1
RStart IN2
REnd IN2
Difference
Diff RStart
Diff REnd
CJ Sensor
CJ RTDBase
Con. IN AO
Con. IN SW1
Mode SW1
SPL SW1
SPH SW1
fig @986 3::
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 29
11.8 Key for output
11.8.1 Key for output configuration (analog output)
Configuration selection, output configuration
Access to the menu items for the configuration of the output
(see “Key for output configuration (analog output)” on page 29)
Setting for the dependent parameters of the analog output – mode, start and end of range, display of cor-
rection values, fault behavior (OR, UR, LB, KS)
Monitoring of output load/short circuit (Yes/No), only configurable with SIL = OFF
Resets the correction values of the output
Output
Outp. Conf
Check
B/LB
Reset Cor.
Overrange Underrange
RangeStart RangeEnd
Linebreak
Corr. Start
Shorted
Corr. End
OK / ESC OK
OK
OK
OK
OK
OK
OK
Output Configuration
Outp. Conf
Outp. Conf
Outp. Conf
ESC OK
Start of range for output – setting only possible with SIL = OFF, 4 mA (0 ... 20 mA, -10 ... 10 V)
End of range for output – setting only possible with SIL = OFF, 20 mA (0 ... 20 mA, -10 ... 10 V)
Display of the start correction value for the analog output (mA, V)
Display of the end correction value for the analog output (mA, V)
Analog output value when overrange NE43 Upsc. / NE43 Downsc.
(Configurable for fault behavior = freely definable)
Analog output value for underrange NE43 Upsc. / NE43 Downsc.
(Configurable for fault behavior = freely definable)
Analog output value in the event of line break NE43 Upsc. / NE43 Downsc.
(Configurable for fault behavior = freely definable)
Analog output value in the event of a short circuit on the line NE43 Upsc. / NE43 Downsc.
(Configurable for fault behavior = freely definable)
RangeStart
RangeEnd
Corr.Start
Corr.End
Overrange
Underrange
Linebreak
Shorted
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 30
11.9 Key for error handling
11.10 Key for switch
12 IFS-OP-UNIT operator interface
error codes
The following error codes are shown directly in the display
of the IFS-OP-UNIT operator interface when they occur.
Setting for the fault behavior (NE43 increasing, NE43 decreasing, freely definable)
Access to the menu items for setting the switching output
Access to the menu items for setting the switching output
Setting for the switch-on delay for the switching output (0 ... 10 s)
Setting for the off delay for the switching output (0 ... 10 s)
Manually acknowledge switching output (latching) (Yes/No)
Behavior for switching output in the event of an error - line break (on, off, no response)
Behavior for switching output in the event of an error - short circuit (on, off, no response).
Err.handl.
Switch
Switch 1
On-Delay
Off-Delay
Acknowled.
Linebreak
Shorted
Error code Description
Error 0 Copy error
Module type in the IFS-OP-UNIT is differ-
ent from the connected module.
Error 1,2,3 Checksum error
Please contact Phoenix Contact.
www.9hoenixcomacl. net/catalog
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 31
13 Configuration with the service PC
When making changes to the configuration data, use the
IFS-CONF software
(free download: www.phoenixcontact.net/catalog).
Connect the device and PC with the help of the IFS-
USB-PROG-ADAPTER programming adapter (Order
No. 2811271).
Figure 9 IFS-USB-PROG-ADAPTER
Changes to the configuration and parameterization data can
be made during operation with a connected Ex measuring
circuit as well as in a disconnected state.
13.1 System requirements
IBM PC or compatible computer with 400 MHz or higher
with at least 256 Mbyte RAM
At least 15 Mbyte available hard disk space
Free USB interface, at least USB 1.1.
Screen resolution of 1024 x 768 pixels
Windows 2000 SP4, Windows XP SP2
13.2 Configuring the user characteristic curve
The user characteristic curve is created with the PC-based
IFS-CONF software and stored in the temperature trans-
ducer.
14 Comparison of safety data
Safety data for the
The values for Uo, Io, Po, Lo and Co can be found under
“Safety data according to ATEX for intrinsically safe circuits”
on page 8.
Requirements for intrinsic safety (simple circuits):
Ui Uo
Ii Io
Pi Po
Li + Lc Lo
Ci + Cc Co
(Lc and Cc depend on the cables/lines used).
Information on configuration, parameterization
and service options (e.g., online monitoring) and
their execution can be found in the online help of
the software and in the associated user manuals
of the DTMs (Device Type Manager).
The drivers for the IFS-USB-PROG-ADAPTER
USB programming adapter are installed automat-
ically.
PWR
DAT
ERR
DO
1
4.2
5.2
2.2
3.2
4.3
5.3
2.3
3.3
MACX MCR-EX-T-UI-UP
32825 Blomberg, Germany
MACX MCREXTUIUP
Ord.No.: 2865654
ExTemperature Transducer/ExTemperaturmessumformer
Supply Voltage:
Input
AnalogOut
DigitalOut
Max. Values
24V ... 230V AC/DC
RTD, TC, mV, Poti, R
020mA / ± 10V
WARNING
DO NOT SEPARATE WHEN ENERGIZED
AND INSTALLED IN ZONE 2
www.phoenixcontact.com
see manual
(20%...+10%, 50Hz/60Hz)
U= 253V
m
U= 253V
m
U= 6,0 V DC
O
T20°...+65°C/4°...+14F
amb
0,5A (30V AC) / 1A (30V DC)
I= 7,4 mA
O
P= 11 mW
O
U= 30V (Zone 2)
m
P= 1,5W
N
OUT
IN
GND
14
11
12
NC
I
out
U
out
1.12.1
5.1
3.1
4.1
1.22.2
5.2
3.2
4.2
1.32.3
5.3
3.3
4.3
+
S-PORT
μc
3.1 3.2 3.3
2.1 2.2 2.3
1.1 1.2 1.3
Freely configurable user characteristic curve for
individual adaptation of resistance temperature
detectors (RTD) and thermocouples (TC).
The user characteristic curve is either selected
with the IFS-CONF or with the IFS-OP-UNIT soft-
ware.
WARNING: Explosion hazard
Compare the safety data before connecting a de-
vice located in the intrinsically safe area to the
MACX MCR-EX-T-UI-UP....
Field devices: Ui, Ii, Pi, Li, Ci
Temperature transducers: Uo, Io, Po, Lo, Co
Connectlon example 2: Input: Thermocouple with internal cold junction compensation 0 Use the MACX MCR-EX-CJC cold junction 1 compensation connector provided (Order No. 2925002). Currenloutput (4 20 mA) on passive safe controller I» .9 out G> nun . um "our 15.2 Voltage output Connemlon example: Input: Potentiometer Output: Voltage output (-10 10 V) on pass controller I nanLenJM PHOENIX CONTA
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 32
15 Application examples
15.1 Current output
Connection example 1:
Connection example 2:
Connection example 3:
15.2 Voltage output
Connection example:
Input: 4-wire RTD
Output: Current output (4 ... 20 mA) on passive safe
controller
Input: Thermocouple with internal cold junction
compensation
Output: Current output (4 ... 20 mA) on passive safe
controller
PLC / DCS
IN OUT
Power
24V ...230V AC/DC
3.3
3.1
1.2
3.2
1.1
2.3
2.1
2.2
1.3
4.3
4.1
4.2
5.3
5.1
5.2
μC
S-PORT
GND
I
U
OUT
OUT
NC
ϑ
Sensor / Field
Zone 0,1,2
Zone 20,21,22
Use the MACX MCR-EX-CJC cold junction
compensation connector provided (Order No.
2925002).
PLC / DCS
Zone 0,1,2
Zone 20,21,22
IN OUT
Power
24V ...230V AC/DC
3.3
3.1
1.2
3.2
1.1
2.3
2.1
2.2
1.3
4.3
4.1
4.2
5.3
5.1
5.2
μC
S-PORT
GND
I
U
OUT
OUT
NC
Sensor / Field
TC -
+
Input: Thermocouple with external or without in-
ternal cold junction compensation or volt-
age input
Output: Current output (4 ... 20 mA) on passive safe
controller
Input: Potentiometer
Output: Voltage output (-10 ... 10 V) on passive
controller
PLC / DCS
Zone 0,1,2
Zone 20,21,22
IN OUT
Power
24V ...230V AC/DC
3.3
3.1
1.2
3.2
1.1
2.3
2.1
2.2
1.3
4.3
4.1
4.2
5.3
5.1
5.2
μC
S-PORT
GND
I
U
OUT
OUT
NC
Sensor / Field
TC -
+
=mV
PLC / DCS
INOUT
Power
24V ...230V AC/DC
3.3
3.1
1.2
3.2
1.1
2.3
2.1
2.2
1.3
4.3
4.1
4.2
5.3
5.1
5.2
μC
S-PORT
GND
I
U
OUT
OUT
NC
Sensor / Field
Poti
Zone 0,1,2
Zone 20,21,22
I nlsnLenJfl
MACX MCR-EX-T-UI-UP...
104601_en_04 PHOENIX CONTACT 33
15.3 Switching output
Connection example:
Input: 3-wire RTD
Output: Voltage output (-10 ... 10 V) on passive
controller
Switching
output:
Dependent on selected switching behavior
PLC / DCS
INOUT
Power
24V ...230V AC/DC
3.3
3.1
1.2
3.2
1.1
2.3
2.1
2.2
1.3
4.3
4.1
4.2
5.3
5.1
5.2
μC
S-PORT
GND
I
24 V
OUT
OUT
NC
Sensor / Field
ϑ
DI
Zone 0,1,2
Zone 20,21,22
Appendix - Safety-related applications (SIL 2)
en Version 04 PHOENIX CONTACT A-1
Appendix
A1 Safety-related applications (SIL 2)
Valid hardware and firmware versions
SIL regulations apply to the following modules:
The safety-related temperature transducers listed above
from the MACX MCR(-EX)-T-... series have been evaluated
by exida Certification S.A. via a Full Assessment in accor-
dance with IEC 61508 Ed.1.0 to SIL 2.
Certificate number: Phoenix Contact 100134C P0019
C001.
A1.1 Safety function and safety requirements
The safety-related measuring transducers are used for the
acquisition of a sensor signal (RTD, TC sensors, resistance-
type sensors, mV sources), that is converted into a scaled
signal and from which a standardized “life zero” current sig-
nal is generated. The entire conversion is continuously mon-
itored to a maximum transmission error of 5%. In the event
of greater deviations, the device switches to the safe state.
The safe state is an output signal of either < 3.6 mA or > 21
mA.
With the REL versions, an additional signal is generated,
which is compared with up to two specified switching thresh-
olds. When the first threshold is reached, the safety relay is
switched on without confirmation contact and when the sec-
ond threshold is reached, it is switched off. Depending on
the application, the safety for the switching output is imple-
mented by either the series or parallel connection of relays
2 and 3, a fuse connected in series, and by monitoring the
calculated switching value. In the event of deviations of
more than 5%, the device switches to the safe state. The
safe state in this case is an uncontrolled relay.
The hardware is also continuously monitored. If an internal
failure is detected, the measuring transducer also switches
to the safe state (current output < 3.6 mA or > 21 mA or un-
controlled relay).
The transition to the safe state always takes place within the
internal failure detection time of 50 s.
The measuring transducer is released (restarted) by switch-
ing off the supply voltage and switching it back on again, by
resetting the transducer via the serial interface, or by activat-
ing the “Restart” option during configuration. The integrated
startup tests are then performed. If the error is still present,
it will be detected during these tests. If it is still present, the
measuring transducer switches back to the safe state.
In addition to the safety functions, there are also monitoring
functions for the input and the current output.
Evaluation
Failures which are detected in the measuring transducer
and to which the transducer responds by switching to the
safe state are safe failures (λs).
Failures where the measuring transducer does not follow a
change of input signal or generates an output signal that de-
viates from the intended value by more than ±5%, are eval-
uated as dangerous failures (λd).
Both safe (λs) and dangerous (λd) failures can be detected
by diagnostic measures. Detected dangerous failures (λdd)
are handled in the same way as safe failures.
The monitoring functions refer to events whose cause is
detected and reported outside of the device.
NOTE: Only those devices with SIL designa-
tion and device firmware with revision 0.92 or
higher are certified for SIL 2.
Designation Order No.
Standard configuration
MACX MCR-T-UI-UP 28 11 394
MACX MCR-T-UI-UP-SP 28 11 860
MACX MCR-T-UIREL-UP 28 11 378
MACX MCR-T-UIREL-UP-SP 28 11 828
MACX MCR-EX-T-UI-UP 28 65 654
MACX MCR-EX-T-UI-UP-SP 29 24 689
MACX MCR-EX-T-UIREL-UP 28 65 751
MACX MCR-EX-T-UIREL-UP-SP 29 24 799
Order configuration
MACX MCR-T-UI-UP-C 28 11 873
MACX MCR-T-UI-UP-SP-C 28 11 970
MACX MCR-T-UIREL-UP-C 28 11 514
MACX MCR-T-UIREL-UP-SP-C 28 11 831
MACX MCR-EX-T-UI-UP-C 28 11 763
MACX MCR-EX-T-UI-UP-SP-C 29 24 692
MACX MCR-EX-T-UIREL-UP-C 28 65 722
MACX MCR-EX-T-UIREL-UP-SP-C 29 24 809
NOTE: The evaluation unit following the measur-
ing transducer (e.g., safety-related PLC) must
recognize these states and correspondingly con-
trol the actuator as the final link in the safety chain.
Appendix - Safety-related applications (SIL 2)
en Version 04 PHOENIX CONTACT A-2
Summary:
Together with the actual signal transmission, continuous
checks and diagnostic functions are performed in the mea-
suring transducers in order to detect faulty behavior.
The internal failure monitoring time (diagnostics test in-
terval) is the time taken to carry out and repeat these tests in
full. Random hardware faults are detected during this time.
The internal failure monitoring time is 50 seconds.
A1.2 Safety integrity requirements
A1.2.1 Failure rates: MACX MCR(-EX)-T-UIREL-UP
(-SP)(-C)
Type B device (according to EN 61508-2)
Safety Integrity Level (SIL) 2
–HFT = 0
1oo1d architecture
The total failure rate is: 1.34 * 10-6
The MTBF (Mean Time Between Failures) is therefore
85 years.
The probability of a dangerous failure per hour for “continu-
ous demand” mode and the average probability of failure of
the specified function for “low demand” mode are deter-
mined from the error rate:
PFDavg values
PFH* = 4.3 * 10-8/h
The calculation is performed assuming a checking interval
(TPROOF) of 1 year and a repair time (MTTR) of 24 hours, a
test coverage (CPT) of 95% and a life time (LT) of 10 years.
On the basis of the value determined for the average proba-
bility of failure PFDavg, the checking interval can be in-
creased to up to 5 years.
The values are valid under the following conditions:
The failure rates of the components used remain con-
stant throughout the period of use.
The propagation of failures by the device in the system
is not taken into consideration.
The repair time (replacement) is 24 hours.
The failure rates of the external power supply unit are
not taken into consideration.
The average temperature at which the device is to be
used is 40°C. In this case, normal industrial conditions
are assumed.
The specified failure rates are based on an average am-
bient temperature of 40°C. For an average ambient
temperature of 60°C, the failure rates must be multiplied
by factor 2.5. Factor 2.5 is based on guide values.
Safety/monitor-
ing function
Output sig-
nal range
Safe
state
Reason
Safety function 4 ... 20 mA < 3.6 mA;
or
> 21 mA
Relay is
not con-
trolled
Deviation
> 5%
Input
monitoring
4 ... 20 mA 2 - 3.6
mA; >
21 mA
Line fault input
Output monitoring 4 ... 20 mA = 0 mA Line fault out-
put
As a result of the multiple connection options,
only two device types are considered in the con-
figurations for “RTD 3-wire” or “mV” in the follow-
ing. They represent all configurations with a
variable resistance at the input terminals or volt-
age or thermocouple inputs and always indicate
the most conservative case. The two device types
are:
1. MACX MCR(-EX)-T-UI-UP(-SP)(-C)
2. MACX MCR(-EX)-T-UIREL-UP(-SP)(-C)
FIT (Failure In Time)
1 FIT is 1 failure in 109 hours
Input: RTD 3-wire connection method
Output: Switching output 2 and 3 (redundant)
λSD λSU λDD λDU SFF DCD
02.34 *
10-7
5.43*
10-7
0.43 *
10-7 94% 92 %
0 FIT 234 FIT 543 FIT 43 FIT
T[PROOF] = 1 year 2 years 5 years
PFDavg = 2.88 * 10-4 4.67 * 10-4 1.01 * 10-3
Appendix - Safety-related applications (SIL 2)
en Version 04 PHOENIX CONTACT A-3
1.2.2 Failure rates: MACX MCR(-EX)-T-UIREL-UP
(-SP)(-C)
Type B device (according to EN 61508-2)
Safety Integrity Level (SIL) 2
–HFT = 0
1oo1d architecture
The total failure rate is: 1.34 * 10-6
The MTBF (Mean Time Between Failures) is therefore
85 years.
The probability of a dangerous failure per hour for “continu-
ous demand” mode and the average probability of failure of
the specified function for “low demand” mode are deter-
mined from the error rate:
PFDavg values
PFH* = 5.6 * 10-8/h
The calculation is performed assuming a checking interval
(TPROOF) of 1 year and a repair time (MTTR) of 24 hours, a
test coverage (CPT) of 95% and a life time (LT) of 10 years.
On the basis of the value determined for the average proba-
bility of failure PFDavg, the checking interval can be in-
creased to up to 5 yearsif the percentage of the device for
the entire loop is assumed at 10%.
The values are valid under the following conditions:
The failure rates of the components used remain con-
stant throughout the period of use.
The propagation of failures by the device in the system
is not taken into consideration.
The repair time (replacement) is eight hours.
The failure rates of the external power supply unit are
not taken into consideration.
The average temperature at which the device is to be
used is 40°C. In this case, normal industrial conditions
are assumed.
The specified failure rates are based on an average am-
bient temperature of 40°C. For an average ambient
temperature of 60°C, the failure rates must be multiplied
by factor 2.5. Factor 2.5 is based on guide values.
1.2.3 Failure rates: MACX MCR(-EX)-T-UI-UP(-SP)
(-C)
Type B device (according to EN 61508-2)
Safety Integrity Level (SIL) 2
–HFT = 0
1oo1d architecture
The total failure rate is: 1.18 * 10-6
The MTBF (Mean Time Between Failures) is therefore
97 years.
The probability of a dangerous failure per hour for “continu-
ous demand” mode and the average probability of failure of
the specified function for “low demand” mode are deter-
mined from the error rate:
PFDavg values
PFH* = 4.3 * 10-8/h
The calculation is performed assuming a checking interval
(TPROOF) of 1 year and a repair time (MTTR) of 24 hours, a
test coverage (CPT) of 95% and a life time (LT) of 10 years.
On the basis of the value determined for the average proba-
bility of failure PFDavg, the checking interval can be in-
creased to up to 5 years.
The values are valid under the following conditions:
The failure rates of the components used remain con-
stant throughout the period of use.
The propagation of failures by the device in the system
is not taken into consideration.
Input: Voltage input mV
Output: Switching output 2 and 3 (redundant)
λSD λSU λDD λDU SFF DCD
02.38 *
10-7
5.22*
10-7
0.56 *
10-7 93% 90%
0 FIT 238 FIT 522 FIT 56 FIT
T[PROOF] = 1 year 2 years 5 years
PFDavg = 3.67 * 10-4 5.99 * 10-4 1.30 * 10-3
Input: RTD 3-wire connection method
Output: 4 ... 20 mA (current output)
λSD λSU λDD λDU SFF DCD
0 0 8.05*
10-7
0.43 *
10-7 94% 94%
0 FIT 0 FIT 805 FIT 43 FIT
T[PROOF] = 1 year 2 years 5 years
PFDavg = 2.95 * 10-4 4.76 * 10-4 1.02 * 10-3
Appendix - Safety-related applications (SIL 2)
en Version 04 PHOENIX CONTACT A-4
The repair time (replacement) is eight hours.
The failure rates of the external power supply unit are
not taken into consideration.
The average temperature at which the device is to be
used is 40°C. In this case, normal industrial conditions
are assumed.
The specified failure rates are based on an average am-
bient temperature of 40°C. For an average ambient
temperature of 60°C, the failure rates must be multiplied
by factor 2.5. Factor 2.5 is based on guide values.
1.2.4 Failure rates: MACX MCR(-EX)-T-UI-UP(-SP)
(-C)
Type B device (according to EN 61508-2)
Safety Integrity Level (SIL) 2
–HFT = 0
1oo1d architecture
The total failure rate is: 1.19 * 10-6
The MTBF (Mean Time Between Failures) is therefore
96 years.
The probability of a dangerous failure per hour for “continu-
ous demand” mode and the average probability of failure of
the specified function for “low demand” mode are deter-
mined from the error rate:
PFDavg values
PFH* = 5.6 * 10-8/h
The calculation is performed assuming a checking interval
(TPROOF) of 1 year and a repair time (MTTR) of 24 hours, a
test coverage (CPT) of 95% and a life time (LT) of 10 years.
On the basis of the value determined for the average proba-
bility of failure PFDavg, the checking interval can be in-
creased to up to 5 years.
The values are valid under the following conditions:
The failure rates of the components used remain con-
stant throughout the period of use.
The propagation of failures by the device in the system
is not taken into consideration.
The repair time (replacement) is eight hours.
The failure rates of the external power supply unit are
not taken into consideration.
The average temperature at which the device is to be
used is 40°C. In this case, normal industrial conditions
are assumed.
The specified failure rates are based on an average am-
bient temperature of 40°C. For an average ambient
temperature of 60°C, the failure rates must be multiplied
by factor 2.5. Factor 2.5 is based on guide values.
A1.3 Configuring an SIL device
The measuring transducer can be ordered with a standard
configuration (see 1.) or configured for safety-related appli-
cations (see 2.), or can be configured by users themselves
for safety-related applications (see 3.).
1. The measuring transducers are delivered with a stan-
dard configuration for safety-related applications with a
4 - 20 mA output (see order key).
2. Customer-specific pre-configured devices (-C) can be
delivered for both safety-related applications and “nor-
mal” usage. Configuration data is shown on a label.
3. The measuring transducers can also be configured by
users for both safety-related applications and “normal”
usage.
The configuration can be read out and changed at any time
for all devices.
Input: Voltage input mV
Output: 4 ... 20 mA (current output)
λSD λSU λDD λDU SFF DCD
0 0 7.89*
10-7
0.56 *
10-7 93% 93%
0 FIT 0 FIT 789 FIT 56 FIT
T[PROOF] = 1 year 2 years 5 years
PFDavg = 3.75 * 10-4 6.08 * 10-4 1.31 * 10-3
For safety-related applications, the password set
in the factory must always be changed.
If the password is lost, it is not possible to change
the configuration.
In this case, please contact Phoenix Contact.
www.moenixconlacl. neI/calalog D9996 www.moenixconlacl.net/calalog.
Appendix - Safety-related applications (SIL 2)
en Version 04 PHOENIX CONTACT A-5
Configuring safety-related applications
Connect the device and PC with the help of the IFS-
USB-PROG-ADAPTER programming adapter (Order
No. 2811271).
Load the IFS-CONF configuration software (free down-
load at:
www.phoenixcontact.net/catalog).
Further information on the FDT frame application (IFS-
CONF) and the device drivers (DTM) can be found in
the IFS-CONF user manual.
Read out the active configuration.
Enter the password in the IFS-CONF in the “PIN” hard-
ware configuration (set to 1111 in the factory).
Activate/deactivate SIL.
In the case of “SIL ON”, it is also possible to deactivate the
Restart after failsafe” item here.
This means that in the event of a failure, the measuring
transducer enters the failsafe state according to the safety
functions, but is not restarted.
Write the modified configuration data to the measuring
transducer.
Check that the new configuration data in the control
window is correct and confirm with “OK” or “Cancel” if
not correct.
A1.4 Installation and startup
During installation, always observe the package slips
The package slip is supplied with the device. It can also be
downloaded at: www.phoenixcontact.net/catalog.
Lockable housing with IP54 protection is recommended for
the installation of the measuring transducer.
Check that the configuration of the measuring transduc-
er is correct for the intended application.
Connect the measuring transducer according to the in-
stallation instructions.
Make sure that the connected sensor corresponds to
the configuration.
Check the functionality of the measuring transducer
with connected sensor for correct function.
A calibrated sensor simulator (RTD/TC) and a calibrat-
ed digital multimeter are necessary for checking the
measuring transducer.
Start up the loop and check that it operates correctly.
A1.5 Notes on operation
Only the green LED (PWR) is on during normal operation.
If a malfunction occurs during operation and the red LED
(ERR) flashes, there is a line fault. The output current of the
measuring transducer is between 2 … 3.6 mA or is higher
than 21.0 mA (in the case of faults in the sensor circuit) or is
0 mA (in the case of a line break in the output circuit).
Check all signal lines. The device will automatically switch
back to normal operation after the fault has been eliminated.
If a fault occurs during operation and the red LED (ERR) is
permanently on, the device has switched to the “safe state”
(output current is less than 2 mA).
Restart the device in order to return it to normal operation.
If no PC/laptop has been connected, you can also inter-
rupt the power supply.
Or you can carry out a warm start with the help of the
configuration software (Service > Reset).
The measuring transducer should then return to normal op-
eration. If it does not, the measuring transducer must be re-
placed.
NOTE: Installation, operation, and maintenance
may only be carried out by qualified specialist per-
sonnel.
WARNING: If Functional Safety is activated by a
reconfiguration or changes are made to the active
Functional Safety configuration, the rules under
“Installation and startup” must be observed.
WARNING: Limitations on safety-related ap-
plications
Only 4 ... 20 mA, limited programming of output
current in the event of line faults
(2 mA IOut 3.6 mA or IOut 21 mA)
WARNING: Once new configuration data has
been written, the device performs a warm start
that changes the properties of the device. The fol-
lowing control device must be adapted to these
modifications.
WARNING: The device must be write-protected
to prevent improper use. Write protection is cre-
ated by assigning a password.
Designation MNR No.
PACKB.MACX MCR-T-UI-UP... 9055145
PACKB.MACX MCR-EX-T-UI-UP... 9055147
PACKB.MACX MCR-T-UIREL-UP... 9055146
PACKB.MACX MCR-EX-T-UIREL-UP... 9055148
Appendix - Safety-related applications (SIL 2)
en Version 04 PHOENIX CONTACT A-6
A1.6 Recurring checks (SIL 2)
The function of the entire safety loop must be checked reg-
ularly according to EN 61508 and EN 61511. The intervals
for checking are specified by the intervals of each individual
device within the safety loop.
It is the operator's responsibility to select the type of checks
and the checking intervals in the specified time period.
The measuring transducers must be checked at least every
7 years (maximum proof test interval).
Checking must be carried out in such a way that the correct
function of the safety equipment in conjunction with all com-
ponents can be verified.
Possible procedure for recurring checks for discover-
ing dangerous and undetected device failures.
A calibrated sensor simulator (RTD/TC) and a calibrated
digital multimeter are necessary for checking the measuring
transducer.
Connect the sensor simulator to the input of the mea-
suring transducer using the appropriate connection
method.
Connect the digital multimeter to the output in current
measuring mode (20 mA range).
The measuring range limits and intermediate values are
specified with the sensor simulator.
The corresponding output values of the measuring trans-
ducer must be checked on the digital multimeter.
Line faults (break and short circuit) are to be simulated on
the input terminals; the configured residual currents are to
be determined on the output.
If the function test result is negative, the measuring trans-
ducer must be taken out of operation and the process put
into a safe state by other measures.
A1.7 Repair
The devices have a long service life, are protected against
malfunctions, and are maintenance-free. However, if a de-
vice should fail, send it back to Phoenix Contact immedi-
ately. The type of malfunction and possible cause must also
be stated.
Please use the original packaging or other suitable safe
packaging when sending devices back for repairs or recali-
bration.
Phoenix Contact GmbH & Co KG
Abteilung Service und Reparatur
Flachsmarktstr. 8
D-32825 Blomberg
GERMANY
A1.8 Standards (SIL 2)
The measuring transducers are developed and tested ac-
cording to the following standards:
EN 61508:
2001
Functional safety of electrical/electronic/
programmable electronic safety-related
systems
EN 61326-1:
2006
Electrical equipment for measurement,
control and laboratory use – EMC re-
quirements
IEC 61326-3-2:
2006
Electrical equipment for measurement,
control and laboratory use – EMC re-
quirements – Part 3-2: Immunity require-
ments for safety-related systems and for
equipment intended to perform safety-
related functions (functional safety) – In-
dustrial applications with specified elec-
tromagnetic environment
Appendix - Safety-related applications (SIL 2)
en Version 04 A-7
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
www.phoenixcontact.com
A1.9 Abbreviations
Abbreviation Meaning
DCDDiagnostic Cov-
erage of Dan-
gerous Failures
Diagnostic coverage:
DCD = λDD/(λDU + λDD)
HFT Hardware Fault
Tolerance
Hardware Fault Tolerance:
Ability of a function unit to con-
tinue with the execution of a de-
manded function despite exist-
ing failures or deviations
λDRate of Danger-
ous Failures
Proportion of dangerous fail-
ures per hour
λDD Rate of Danger-
ous Detected
Failures
Proportion of detected danger-
ous failures per hour
λDU Rate of Danger-
ous Undetected
Failures
Proportion of undetected dan-
gerous failures per hour
λSRate of Safe
Failures
Proportion of safe failures per
hour
MTBF Mean Time
Between
Failures
Mean time between consecu-
tive failures
PFDavg Average
Probability of
Failure on
Demand
Average probability of failure on
demand of a safety function
PFH Probability of a
Dangerous
Failure per Hour
Probability of failure per hour
for the safety function
SFF Safe Failure
Fraction
Proportion of safe failures: Pro-
portion of failures without the
potential to set the safety-re-
lated system to a dangerous or
impermissible function state
SIL Safety Integrity
Level
International standard IEC
61508 defines four discrete
safety integrity levels (SIL 1 to
4). Each level corresponds to a
probability range for the failure
of a safety function. The higher
the safety integrity level of
safety-related systems, the
lower the probability that the
demanded safety functions will
not be performed.